VTS-Supervision Module - Voltage Transformer Supervision [60FL]
Voltage Transformer Supervision Module Input States
Name
Description
Assignment via
Ex Fuse Fail VT-I
Module input state: External fuse failure
voltage transformers
[Protection Para
/Global Prot Para
/Supervision
/VTS]
Ex Fuse Fail EVT-I
Module input state: External fuse failure
earth voltage transformer
[Protection Para
/Global Prot Para
/Supervision
/VTS]
ExBlo1-I
Module input state: External blocking1
[Protection Para
/Global Prot Para
/Supervision
/VTS]
ExBlo2-I
Module input state: External blocking2
[Protection Para
/Global Prot Para
/Supervision
/VTS]
Voltage Transformer Module Signals (Output States)
Name
Description
active
Signal: active
ExBlo
Signal: External Blocking
Alarm ΔV
Signal: Alarm ΔV Voltage Transformer Measuring Circuit
Supervision
Alarm
Signal: Alarm Voltage Transformer Measuring Circuit Supervision
Ex FF VT
Signal: Alarm Fuse Failure Voltage Transformers
Ex FF EVT
Signal: Alarm Fuse Failure Earth Voltage Transformers
EN MRU4 10/09