Module: Digital Inputs (DIs)
Digital Inputs (Standard)
DI Slot X1
Global Protection Parameters of the Digital Inputs (Standards)
Parameter
Description
Setting range
Default
Menu path
Nom voltage
Nominal voltage of the
digital inputs
24 V DC,
48 V DC,
60 V DC,
110 V DC,
230 V DC,
110 V AC,
230 V AC
24 V DC
[Device Para
/Digital Inputs
/DI Slot X1
/Group 1]
Inverting 1
Inverting the input
signals.
inactive,
active
inactive
[Device Para
/Digital Inputs
/DI Slot X1
/Group 1]
Debouncing time 1
A change of the state of a
digital input will only be
recognized after the
debouncing time has
expired (become
effective). Thus, wipers
will not be misinterpreted.
no debouncing time,
20 ms,
50 ms,
100 ms
no debouncing time
[Device Para
/Digital Inputs
/DI Slot X1
/Group 1]
Nom voltage
Nominal voltage of the
digital inputs
24 V DC,
48 V DC,
60 V DC,
110 V DC,
230 V DC,
110 V AC,
230 V AC
24 V DC
[Device Para
/Digital Inputs
/DI Slot X1
/Group 2]
Inverting 2
Inverting the input
signals.
inactive,
active
inactive
[Device Para
/Digital Inputs
/DI Slot X1
/Group 2]
EN MRU4 10/09
Page 95