All technical data and ratings indicated in this chapter are not definite! Only the values indicated in
Chapter 7: Technical Data on page 30 are valid!
The following chart may be used to convert square millimeters [mm²] to AWG and vice versa:
AWG
mm²
AWG
mm²
AWG
mm²
AWG
mm²
AWG
mm²
AWG
mm²
30
0.05
21
0.38
14
2.5
4
25
3/0
95
600MCM
300
28
0.08
20
0.5
12
4
2
35
4/0
120
750MCM
400
26
0.14
18
0.75
10
6
1
50
300MCM
150
1000MCM
500
24
0.25
17
1.0
8
10
1/0
55
350MCM
185
22
0.34
16
1.5
6
16
2/0
70
500MCM
240
Table 4-1: Conversion chart - wire size
Power Supply
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Figure 4-1: Power supply
Terminal Description
A
max
3
Earth Ground
2.5 mm²
2
12/24Vdc
2.5 mm²
1
0 Vdc
2.5 mm²
Table 4-2: Power supply - terminal assignment
NOTE
Earth Ground Terminal #3 is galvanically connected to aluminum housing. If the housing is assembled
on a grounded metal plate possible ground current loops via terminal #3 are to be considered!