If the LSG mode is set to 1 (EGCP-2) the icon “LSG” at the LDSS screen (easYgen) is twinkling if the CAN
connection between easYgen and LSG is OK. This icon is permanent, if an EGCP-2 in automatic mode is de-
tected on the RS-485 bus. The GCB icon shows closed if one or more EGCP-2 has a closed GCB.
If the LSG mode is set to 9 (GCP/MFR) the icon “LSG” at the LDSS screen (easYgen) is twinkling if the CAN
connection between easYgen and LSG is OK. This icon is permanent, if a GCP/MFR is detected on the CAN bus.
The GCB icon shows closed if one or more GCP/MFR has a closed GCB.
In analog mode “LSG” at the LDSS screen is permanent if the CAN connection between easYgen and LSG is
OK. The GCB icon shows closed if at least one easYgen device, which is connected via CAN to the LSG, has a