Manual 37351A
MFR 11 Packages - Protection Relay
Page 16/59
© Woodward
Interface
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
DPC - Direct Configuration Interface
NOTE
Configuration with the direct configuration cable DPC (P/N 5417-557) is possible. A laptop/PC, the DPC
cable, the program LeoPC1 version 3.1.1 or higher (included on CD Rom with unit), and the proper con-
figuration files are required. Please consult the online help installed when the program is installed for a
description of the LeoPC1 program and its setup.
WARNING
Only the DPC cable may be connected to the DPC interface. If other devices or lines are connected, the
unit may be destroyed. Especially the connection of live lines (like phone lines) will destroy the unit.
CAUTION
The connection cable delivered with the DPC must be used between DPC and the unit to ensure proper
functionality of the unit. An extension or utilization of different cable types for the connection between
the unit and DPC may result a malfunction of the unit. This may possibly result in damage to compo-
nents of the system. If an extension of the data connection line is required, only the serial cable (RS-
232) between DPC and laptop/PC may be extended. It is recommended to use an industry standard ca-
ble for this.
NOTE
If the parameter "Direct config." is enabled on the control, communication via the CAN bus interface on
terminals X1/X5 is disabled.
If the control unit detects that the engine is running (ignition speed exceeded), the direct configuration
port is disabled.