Manual 37351A
MFR 11 Packages - Protection Relay
Page 10/59
© Woodward
Chapter 3.
Installation
Wiring Diagram 100/400 V Package Models (Standard)
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
su
per
vi
sed sy
st
em
(
var
ia
bl
e)
Subject to technical modifications.
7
8
CB
3/
4
Relay 2
Relay 1
(Ready for operation)
2005-09-13 | MFR 11 Wiring Diagram r13ww-3705-ap.skf
12
11
10
9
13
16
15
14
Pac
k.
SC
5
6
70
71
72
1
2
4
3
Measuring voltage L1
not measured
Blocking of protective functions
or remote acknowledgement
Synchronizing voltage L2
Synchronizing voltage L1
Synchronizing voltage L3
Measuring voltage
three-wire or
four-wire system
Measuring voltage L2
Measuring voltage L3
(Measuring voltage N)
Relay 8
M
F
R
1
1 (
M
ul
ti Func
tion R
el
ay)
Relay 3
(
Package SC
: Synch-check)
Measuring voltage: 100 V AC or 400 V AC
The socket for the PC parameterization is situated
on the side of the unit. This is where the DPC
must be plugged in.
Pac
kage
s G
59
/ G
59
N
all P
ac
ka
ge
s
all P
ac
ka
ge
s
0 Vdc
24 Vdc
Packages SC+N/NU/G59N
: 90 to 265 Vac/dc
27
21
20
19
22
26
25
24
23
28
32
31
30
29
al
l Pa
ck
ag
es
Relay 4
Relay 5
Relay 6
Relay 7
sy
nc
hr
oni
zi
ng sys
te
m
(f
ix
ed
)
The synchronizing voltage must be connected three-
phase if the measuring voltage is connected three-
phase (N not connected). If the measuring voltage is
connected four-phase (L1-L2-L3-N), the synchronizing
voltage may be connected two-phase (L1-L2). L3 is
connected only for compensation and is not measured.
3/
4
2/
3
Figure 3-1: Wiring diagram 100/400 V package models