Screens for Protocol CAN Bus (
Options SU/SB
)
NOTE
Please note that IDs must not be allocated twice. This applies to all units linked to the bus system.
Moreover, all IDs adjusted at the unit must be set to different values.
Procedure for transmission-IDs: The same "Basic-ID Transmission" is allocated to all units existing
within the bus system. This allows a grouping of the various types of information. (Example: The same
"Basic-ID Transmission" = 800 is allocated to all units. By means of the different unit numbers, the in-
dividual IDs are then allocated; unit number 1: ID = 801; unit number 2: ID = 802; etc.)
Device number
CAN-Bus 0
Device number CAN-bus
1 to 8
The device number at CAN-bus is entered here. The device number affects the cal-
culation of the transmitting- and controlling IDs.
Baudrate
0000
Baudrate CAN-Bus
125/250/500kBaud
Setting the baudrate.
Base-ID (send)
0000
Basic - ID Transmission
0 to 2015
The ID, from which the device is transmitting its operating data, is calculated from
the Basic-ID Transm Device Number CAN-Bus.
Base-ID (remote)
0000
Basic - ID control
0 to 2015
The ID, at which the device receives control data, is calculated from the Basic-ID-
C Device Number CAN-Bus.
ID (parametriz.)
0000
ID for remote parameterization
0 to 2015
Here the ID is entered on which the unit receives parameterization data. If the re-
mote parameterization occurs via a system GW 4, these ID's must always be set to
the value 831.