Operation Manual 37107F
MFR 3 - Multi Function Relay
© Woodward
Page 125/165
Outputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Parameter
225
Configure
Outputs YES
Configure outputs
YES/NO
Various groups of parameters are grouped together in blocks to aid in the rapid na-
vigation through the large number of configuration screens. Selecting "YES" or
"NO" does not determine if control or monitoring is performed. The user’s selec-
tion has the following effect:
YES
.............. The configuration screens in this block are displayed and can either
be viewed ("Select" push button) or modifications can be made to the
parameters ("Cursor
→
", "Digit
↑
" or "Select" push buttons). This
does not disable or enable individual parameters, only if the individ-
ual parameters in this parameter block may be accessed for modifica-
tions.
NO
................ The parameters in this block are not displayed, cannot be modified
and are therefore skipped.
Analog Outputs
The analog output manager can be used to apply specific measurement variables to the available analog outputs.
The outputs may be configured as 0 to 20 mA or as 4 to 20 mA. A list of the parameters, which may be confi-
gured, is located in Appendix D. Each parameter is assigned a unique number. The parameter may be scaled via
an upper and a lower input value. The analog outputs may also be assigned an engineering unit of measure (refer
to "Analog output manager" in Appendix D).
NOTE
The list of values and setting limits for the analog output manager is contained in chapter "Analog
Output Manager" starting on page 141.
Possible outputs:
130/131 and 132/133
Example:
Analog output 130/131
Parameter
226
Analg.out.130131
parameter 00
Analog outputs: parameter
0 to 23
The number of the desired measurement variable output is entered here. A list of all
parameters available for configuration, along with the output and limit value
ranges, is located in Appendix D.
Parameter
227
Analg.out.130131
0-00mA
Analog outputs: range
OFF / 0 to 20 / 4 to 20 mA
The output is enabled or disabled and the type of output (0 to 20 mA or 4 to
20 mA) may be selected.
Parameter
228
Analg.out.130131
0% 0000
Analog output: scaling of the lower level
0 to 9,990
The 0 % value for the monitored range is set here: refer to Appendix D.
Parameter
229
Analg.out.130131
100% 0000
Analog output: scaling of the upper level
0 to 9,990
The 100 % value for the monitored range is set here: refer to Appendix D.