Operation Manual 37107F
MFR 3 - Multi Function Relay
© Woodward
Page 151/165
MUX
No.
Content (words)
Unit Comment
23/3 69 Speed detection
Bit 15 = 1
--Internal--
Bit 14 = 1
--Internal--
Bit 13 = 1
--Internal--
Bit 12 = 1
--Internal--
Bit 11 = 1
--Internal--
Bit 10 = 1
--Internal--
Bit 9 = 1
--Internal--
Bit 8 = 1
--Internal--
Bit 7 = 1 \
Bit 6 = 1
Bit 5 = 1
Bit 4 = 1 /
Firing speed exceeded
Bit 3 = 1 \
Bit 2 = 1
Bit 1 = 1
Bit 0 = 1 /
Machine is running
VgenEXPO
Exponent generator voltage
IgenEXPO
Exponent generator current
PgenEXPO
Exponent generator power
VbusEXPO
Exponent busbar voltage
VmainsEXPO
Exponent mains voltage
PmainsEXPO
Exponent mains power
PgenWD
Conversion factor steps kW
Receiving Telegram
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
A Gateway GW 4 may be used for start/stop synchronizing the MFR. The following three data words can be re-
ceived by the MFR. Refer to the GW 4 manual on how to control several MFR units.
MUX
No.
Contents (words)
Unit Note
1/1 1
Set point value for the generator real power
kW
with control argument; see below
1/2 2
Set point value for the generator power fac-
tor cos
ϕ
Example:
FF9EH
cos
ϕ
= c 0.98 (capacitive/lagging)
FF9DH
cos
ϕ
= c 0.99 (capacitive/lagging)
0064H
cos
ϕ
= 1.00
0063H
cos
ϕ
= i 0.99 (inductive/leading)
0062H
cos
ϕ
= i 0.98 (inductive/leading)
1/3 3
Control word
Bit 15 = 1
--Internal--
Bit 14 = 1
--Internal--
Bit 13 = 1
--Internal--
Bit 12 = 1
--Internal--
Bit 11 = 1
--Internal--
Bit 10 = 1
--Internal--
Bit 9 = 1
--Internal--
Bit 8 = 1
--Internal--
Bit 7 = 1
--Internal--
Bit 6 = 1
--Internal--
Bit 5 = 1
--Internal--
Bit 4 = 1
Remote acknowledgement
Bit 3 = 1
Always "0"
Bit 2 = 1
Always "0"
Bit 1 = 1
Remote stop synchronization (high priori-
ty)
Bit 0 = 1
Remote start synchronization