Operation Manual 37107F
MFR 3 - Multi Function Relay
Page 156/165
© Woodward
Option
Parameter
100/400V; 5 A
Setting range
Standard
setting
Customer settings
Lev
el
Configure
Automatic
NO/YES NO
Control via
COM X1X5
ON/OFF OFF
on off
on off
Control via
COM Y1Y5
ON/OFF OFF
on off
on off
Delay to send
MOD to Bus
0.2 to 50.0 ms
CONFIGURE BREAKER
Configure Breaker
YES/NO NO
Y N
Y N
Breaker logic:
see table
PARALLEL
Add-on/off ramp
max.time
0 to 999 s
020 s
Open GCB with F2
max.time
0 to 999 s
010 s
Signal logic GCB
Continuous/Impulse Cont
Opening GCB
NO to cont./NC to cont.
N.O. to con-
tact
CONFIGURE SYNCHRONIZATION
Synchronize df
max
0.02 to 0.49 Hz
0.20 Hz
Synchronize df
min
0.00 to -0.49 Hz
-0.10 Hz
Synchronize dV
max
0.1 to 15 %
01.0 %
Synchronize time
pulse>
0.02 to 0.26 s
0.24 s
Closing time
GCB
40 to 300 ms
080ms
Closing time
MCB
40 to 300 ms
080 ms
Autom.breaker deblocking
ON/OFF OFF
on off
on off
Sync.time contr.
ON/OFF ON
on off
on off
Sync.time contr.
Delay
10 to 999 s
180 s
CONFIGURE DEAD BUSSTART
GCB dead bus op.
ON/OFF ON
on off
on off
GCB dead bus op.
df max
0.05 to 5.00 Hz
0.45 Hz
GCB dead bus op.
dV max
0.1 to 20 %
10,0 %
GCB dead bus op.
max.time
0 to 999 s
030 s
MCB dead bus op.
ON/OFF ON
on off
on off
CONFIGURE BREAKER MONITORING
Supervision GCB
ON/OFF ON
on off
on off
Supervision MCB
ON/OFF ON
on off
on off
Mains decoupling
via
MCB/GCB GCB
Mains settling
time
0 to 999 s
010 s
Mains decouplingvia term.62
ON/OFF OFF
CONFIGURE MONITORING
Configure Monitoring
YES/NO NO
Y N
Y N
Mains power mon.
ON/OFF OFF
on off
on off
Mains power mon.
res.val.
E/I 0 to 16,000 kW
E100 kW
Mains power mon. hysteresis
0 to 999 kW
10 kW
Mains power mon.
Delay
0 to 600 s
1 s
Rev./red.power monitoring
ON/OFF OFF
on off
on off
Rev./red.power resp.value
-99 to 0 to 99 %
-10 %
Rev./red.power Delay
00.1 to 99.9 s
03.0 s
Gen.overload monitoring
ON/OFF OFF
on off
on off
Gen.overload MOP resp.value
80 to 150 %
120 %
Gen.overload MOP
Delay
0 to 99 s
20 s
Gen.overload IOP resp.value
80 to 150 %
105 %
Gen.overload IOP
Delay
0 to 99 s
03 s
Reactive power
Monitoring
ON/OFF OFF
on off
on off
Reactive pow.ind
Limit
5 to 100 %
010 %
Reactive pow.ind
Delay
0 to 600 s
010 s
Reactive pow.cap
Limit
5 to 100 %
010 %
Reactive pow.cap
Delay
0 to 600 s
010 s