Figure 4-4. Shield Termination Diagram 2
Input Power
Branch circuit fuses, breakers, and wiring must have applicable safety approval and be selected according
to applicable codes and area classifications. The system disconnect (not provided) MUST be in easy reach
of the operator and marked as a disconnect device. Each main power supply must have its own branch
circuit rated fuse, or circuit breaker with a rating no more than 250% of the maximum rated current of the
power supply. See
Appendix A
. Do not connect more than one main power supply to any one fuse or
circuit breaker. Use only the wire sizes specified, for the power required, which meet local code
requirements.
Each 5009FT control requires a power source capable of a certain output voltage and current. For AC
sources, this power rating is stated in volt-amps (VA). The maximum VA of a source can be calculated by
taking the rated output voltage times the maximum output current at that voltage. This value should be
greater than or equal to the 5009FT control VA requirement.
Note
: the control’s main power supplies are not equipped with input power switches.
Table 4-1 provides each power supply’s holdup time specification, which is the time the supply will
continue to operate within specification after its input power is interrupted. This information may be useful
in specifying Uninterruptible Power Supply (UPS) systems.
Table 4-1. Fuse/Breaker Requirements
Input Voltage
and
Frequency
Range
Rated
Maximum
Current
Maximum
Fuse/C.B.
Rating
Minimum
Wire Size
mm²/AWG
Wire
Temp.
Rating (°C)*
Hold Up Time
(Minimum)
18–36 Vdc
33 A
50 A
5.5 / 10
90
5 ms @ 24 V
100–150 Vdc
6.0 A
20 A
4.0 / 12
90
7 ms @ 120 V
88–132 Vac
47–63 Hz
10.0 A
20 A
4.0 / 12
90
1 cycle @ 120 V
180–264 Vac
47–63 Hz
5.0 A
10 A
2.5 / 14
90
1 cycle @ 220 V
200–300 Vdc
3.0 A
10 A
2.5 / 14
90
7 ms @ 200 V
*Wire Temp ratings specified are for 55 °C cabinet ambient.
All fuses listed above are “slow blow”.
Significant inrush currents are possible when current is applied to the main power supply. The magnitude
of the inrush current depends on the power source impedance, so Woodward cannot specify the
maximum inrush current. Time- delay fuses or circuit breakers must be used to avoid nuisance trips.
The 5009FT control includes a set of two main power supplies. Input power ratings are identified in Table
4-1 and on each power supply’s front panel. Refer to MicroNet TMR manual
26167
for all power supply
specifications.
Released
Summary of Contents for MicroNet TMR 5009FT
Page 65: ...Manual 26518V2 5009FT Installation Hardware Woodward 63 Figure 8 4 DSLC Control Released...
Page 67: ...Manual 26518V2 5009FT Installation Hardware Woodward 65 Figure 8 5 Real Power Sensor Released...
Page 70: ...Manual 26518V2 5009FT Installation Hardware Woodward 68 Released...
Page 71: ...Manual 26518V2 5009FT Installation Hardware Woodward 69 Released...
Page 72: ...Manual 26518V2 5009FT Installation Hardware Woodward 70 Released...
Page 73: ...Manual 26518V2 5009FT Installation Hardware Woodward 71 Released...
Page 74: ...Manual 26518V2 5009FT Installation Hardware Woodward 72 Released...
Page 75: ...Manual 26518V2 5009FT Installation Hardware Woodward 73 Released...
Page 76: ...Manual 26518V2 5009FT Installation Hardware Woodward 74 Released...
Page 77: ...Manual 26518V2 5009FT Installation Hardware Woodward 75 Released...
Page 78: ...Manual 26518V2 5009FT Installation Hardware Woodward 76 Released...
Page 79: ...Manual 26518V2 5009FT Installation Hardware Woodward 77 Released...
Page 80: ...Manual 26518V2 5009FT Installation Hardware Woodward 78 Released...
Page 81: ...Manual 26518V2 5009FT Installation Hardware Woodward 79 Released...
Page 82: ...Manual 26518V2 5009FT Installation Hardware Woodward 80 Released...
Page 83: ...Manual 26518V2 5009FT Installation Hardware Woodward 81 Released...
Page 84: ...Manual 26518V2 5009FT Installation Hardware Woodward 82 Released...
Page 85: ...Manual 26518V2 5009FT Installation Hardware Woodward 83 Released...
Page 86: ...Manual 26518V2 5009FT Installation Hardware Woodward 84 Released...
Page 87: ...Manual 26518V2 5009FT Installation Hardware Woodward 85 Released...
Page 88: ...Manual 26518V2 5009FT Installation Hardware Woodward 86 Released...
Page 90: ...Manual 26518V2 5009FT Installation Hardware Woodward 88 Released...
Page 91: ...Manual 26518V2 5009FT Installation Hardware Woodward 89 Released...
Page 92: ...Manual 26518V2 5009FT Installation Hardware Woodward 90 Released...
Page 94: ...Manual 26518V2 5009FT Installation Hardware Woodward 92 Declarations Released...