5.5 Adjustment of the fault recorder
The MRN3 is equipped with a fault recorder (see chapter 3.7). Three parameters can be deter-
mined.
5.5.1 Number of the fault recordings
The max. recording time is 16 s at 50 Hz or 13.33 s at 60 Hz.
The number of max. recordings requested has to be determined in advance. There is a choice of
(1)* 2, (3)* 4 or (7)* 8 recordings and dependent on this the duration of the individual fault
recordings is defined, i.e.
(1)* 2 recordings for a duration of 8 s (with 50 Hz) (6.66 s with 60 Hz)
(3)* 4 recordings for a duration of 4 s (with 50 Hz) (3.33 s with 60 Hz)
(7)* 8 recordings for a duration of 2 s (with 50 Hz) (1,66 s with 60 Hz)
* is written over when a new trigger signal arrives
Caution:
If the fault recorder is used, the frequency should be set to f = 50 Hz or f = 60 Hz (see chapter
5.3.3).
5.5.2 Adjustment of trigger occurrences
There is a choice between four different occurrences:
P_UP (Pickup)
Storage is initiated after recognition of a general activation.
TRIP
Storage is initiated after a trip has occurred.
A_PI (After Pickup)
Storage is initiated after the last activation threshold was fallen short of.
TEST
Storing is activated by simultaneous actuation of the keys <+> and <->.
During the recording time the display shows “Test”.
5.5.3 Pre-trigger time (T
pre
)
By the time T
pre
it is determined which period of time prior to the trigger occurrence should be
stored as well. It is possible to adjust a time between 0.05s and the max. recording interval (2, 4
and 8s). With keys <+> and <-> the values can be changed and with <ENTER> be saved.
5.6 Adjustment of the clock
When adjusting the date and time, LED
lights up. The adjustment method is as follows:
Date
:
Year
Y=00
Month
M=00
Day
D=00
Time
:
Hour
h=00
Minute
m=00
Second
s=00
The clock starts with the set date and time as soon as the supply voltage is switched on.
The time is safeguarded against short-term voltage failures (min. 6 minutes).
Note:
The window for parameter setting is located behind the measured value display. The parameter
window can be accessed via the <SELECT/RESET> key.