Manual 26710V1
ProTechTPS Total Protection System
Woodward
29
Protection from direct exposure to sunlight, water, or to a condensation-
prone environments
Protection from high-voltage or high-current devices which produce
electromagnetic interference
Avoidance of vibration
A location that has H
2
S and SO
2
gases at or below the levels classified in
international standard IEC 721-3-3 1994 - environment Class 3C2
Maximum purge pressure: 4 psi
Environmental Specifications
Operating Temperature:
–20 to +60 °C (–4 to +140 °F)
Storage Temperature (non operational): –20 to +65 °C (–4 to +158 °F)
Relative Humidity:
Up to 95% (non-condensing)
Vibration: 0.04
G
2
/Hz, 1.04 Grms, 10 to 500 Hz
Shock:
30 G, 11 ms half-sine pulse
Altitude:
Up to 3000 meters above sea level
Enclosure (Bulkhead Mount Version):
IP56 (per IEC 60529)
Enclosure (Panel Mount Version):
IP56, installed in IP56 enclosure/cabinet
Weight (Bulkhead Mount Version):
Approximately 26 lb (12 kg)
Weight (Panel Mount Version):
Approximately 22 lb (10 kg)
Pollution Degree
2 (per IEC 60664-1)
Overvoltage Category
II (per IEC 60664-1)
Power Supply Requirements
Each ProTechTPS system consists of three separate internal modules (A, B, C),
and each of these three modules accept two input power sources (for
redundancy). Depending on the ProTechTPS model purchased, the internal
modules will accept either two high-voltage (HV) input power sources or one HV
input power source and one low-voltage (LV) input power source. For reliability
purposes, each ProTechTPS module will function normally with power sourced to
both or either power supply input.
Power Supply Specifications
Number of Inputs
2, Input range depends on model (see following
tables):
2 High Voltage Inputs OR
1 High Voltage and 1 Low Voltage
Wiring Constraints
Each power supply input must be provided with its
own breaker. This is to facilitate both on-line-removal
of a module, and also to protect other power supplies
from tripping while connected to a common input
power circuit.
Table 2-1. Input Specifications