Manual WIP1 GB
Woodward
DOK-TD-WIP1 Rev.F
33
From the energizing time displayed can be concluded whether trippings have occurred.
>>Pickup_Time<<<
t>=100%_tE>=2.0%
Date____15.04.97
Time____15:26:45
The exact time the trip occurred is also recorded. After pressing the <SELECT/RESET> push button, mes-
sage „Fault memory 1“ is displayed again.
Example: When selecting an inverse time characteristic a reset time of 300 s is set and the following infor-
mation can be gathered in failure cases:
Number of energizing events
Max. current during each of the energizing events
Duration of the individual energizing events
Time interval between two energizing events
Interval between the energizing phases
Tripping
time
Tripping value at the instant of shut-down