6.5 Protection parameters
6.5.1 Pickup value for phase overcurrent element
The pickup value for the phase overcurrent element I> is displayed as secondary C.T. current in ampere.
>>>Overcurrent<<
I>___=_0.95_A___
If this pickup value is set to "EXIT", the overcurrent trip is blocked.
6.5.2 Time current characteristics for phase overcurrent element
>Characteristic<
Normal_Inverse__
By setting this parameter one of the following nine messages appears on the display:
Definite_time protection:
Definite_time
Inverse_time protection:
Normal_Inverse
Very_Inverse
Extremely Inverse
RI-Inverse
Long Time Inverse
X^2_Time
X^2.5_Time
X^3_Time
X^3.5_Time
X^4_Time
The text displayed can be changed by <+> <-> push buttons. By the <ENTER> push button the required
characteristic is selected.
6.5.3 Trip delay or time multiplier for phase overcurrent element
After the characteristic is changed, usually the time de-lay or time multiplier should be changed accordingly.
>>>Time_Factor<<
tI>_=_0.50______
When the “Inverse time” characteristic has been chosen, the time factor tI> is displayed; this also can gradu-
ally be changed by push buttons <+> and <->.
>>Tripping_Time<
tI>_=_0.35_s____
When the „Definite time“ characteristic has been chosen, the respective time displayed is to be understood in
seconds which can gradually be changed by push buttons <+> and <->.