6.7.3 Earth fault overcurrent
The trip relay can be assigned to the different trip elements and it can be defined whether the earth fault
overcurrent function IE> should result in tripping.
Earth-Fault_IE>_
Alarm___________
In this case alarm means that tripping of the latched re-lay at the electric impulse output and activation of the
LED are prevented. Exceeding of the pickup value incl. expiring of the tripping time is here regarded as acti-
vation only.
6.7.4 Flashing of the Trip-LED
The power that is required for LED flashing is exclusively supplied by the battery. Therefore, it is recom-
mended to shortly reset LED flashing. If this is not possible, the trip indication function of the LED “TRIP” can
be de-activated.
>>TRIP-LED<<<
Flashing______
The LED reset can be done by activating the reset function (please refer to chapter 6.9)
6.7.5 Relay matrix (only relay 2)
This is to determine which functions energize the relay2.
Alarm:
The relay 2 energizes, when a pick-up value of the following protection elements is exceeded.
Trip:
The relay 2 energizes, when the tripping time of the following protection elements is elapsed. At the same
time relay 1, the electric pulse output and the flag indicator output are activated.
The following setting variants are possible:
_I>__Alarm:_Nein
_I>__Trip:__Ja__
_I>>_Alarm:_Nein
_I>>_Trip:__Ja__
IE>__Alarm:_Nein
IE>__Trip:__JA__
IE>>_Alarm:_Nein
IE>>_Trip:__Ja__
The WIP1-1 has a restricted relay assignment function. Relay 2 can only be assigned to tripping functions.
_I>__Trip:__Ja__
_I>>_Trip:__Ja__
IE>__Trip:__JA__
IE>>_Trip:__Ja__