STATUS CODES
During normal boiler operation various Status codes can be displayed by
pressing the
button.
The first screen of the Information menu displays the current Status
code, this will change as the boiler runs through the various modes and
sequences.
These are not always faults, but just provide information concerning the
current status of the boiler.
Status
codes
Fault
codes
200
CH System is being heated
201
DHW system is being heated
202
Anti rapid cycle mode for CH
203
System stand by
204
System waiting, primary flow temperature above
setpoint
205
Waiting for airflow
207
CE
System pressure too low
208
Test mode active due chimney switch
210
E9
Flue-gas thermostat activated
211
TTB opened (thermal kickback device)
212
Safety or flow temperature rises too fast
213
D4
Temperature difference between supply and return
exceeding limit
214
C7
Fan not running
215
C6
Fan running too fast
216
C6
Fan running too slow
217
C7
No airflow after defined period of time
218
E5
Flow temperature too high
219
E9
Safety sensor temperature too high
220
E9
Safety sensor shorted
221
E9
Safety sensor disconnected
222
E2
Flow sensor shorted
223
E2
Flow sensor disconnected
224
E9
MAX thermostat activated
225
Difference between flow and safety exceeding limit
(bi-sensor only)
227
EA
No ionisation detected after ignition
228
F7
Ionisation current detected before burner-start
229
EA
Loss of ionisation signal during operation
230
EA
Ionisation signal out of bounds
231
FD
Mains power error - electrical power interruption
232
D3
external cut-off switch activated
233
9U
HCM problem
234
EA
Gas valve coil disconnected
237
C4
Airflow present during last 24 hours - fan running
continuously
238
F0
Gas valve error
239
F0
Watchdog relay error
240
D1
Return sensor shorted
241
D1
Return sensor disconnected
242 to
256
F0
Internal error call Bosch help line 0844 892 3366
257
b7
Internal error - replace control board
258 &
259
F0
Internal error call Bosch help line 0844 892 3366
260
No temperature rise after burner start
261
EA
First Safety timing error
262 &
263
F0
Internal error call Bosch help line 0844 892 3366
264
C1
Airflow stopped during operation
265
Stand-by mode forced due to energy transfer limit
266
CE
No pressure variation detected after switching pump
267
F0
Watchdog time-out error
268
Component test mode
269
EA
Ignition device activated too long
270
Power up mode
271
D4
Temperature difference between flow and safety
sensor exceeding limit
272
F0
Internal error
273
C4
Airflow present during last 24 hours
274
Ionisation signal present during last 24 hours
276
E9
Flow temperature exceeded 95°
277
E9
Safety sensor temperature exceeded 95°
278
F0
Sensor test failed
279
F0
AD converter error, unstable measurement
280
F0
Recycle timing error
281
A1
Pump stuck or running in air
282
H5
No feedback from pump
283
Burner starting
284
Gas valve(s) opened, first safety time started
285
E9
Return temperature exceeded 95°C
286
D1
Return temperature too high
287
F0
Ionisation sensor shorted
288
CF
Water pressure sensor not connected or short-circuit
to supply
289
CF
Water pressure sensor not connected or short-circuit
to ground
290
F0
AD converter reference error
305
Anti fast cycle mode for DHW
306
FA
Ionisation detected after burner stop
307
Pump stuck
308
Pump running in air
309
CH & DHW system are being heated
310
CUS communication error
311
CUS locked
312
CUS blocked
313
CUS reported error condition
314
Mains disconnected during super lockout
315
Several times lack of water flow
316
E9
Flue gas sensor temperature too high
317
A3
Flue gas sensor shorted
318
E9
Flue gas sensor disconnected
321
Self-test of flue gas supervision
322
Code error
323
A8
EMS communication error
324
DHW-NTC defect
325
DHW-NTC not correctly installed
326
Storage-NTC defect
327
Reset-key stuck or short-circuit
328
Internal error
Status
codes
Fault
codes