background image

NOTE: READ THIS SECTION FULLY BEFORE COMMENCING
INSTALLATION
11.2 GENERAL FITTING.

Check that the appliance carton contains: Appliance, installers
instruction pack, pre-plumbing manifold, wall plate cross
member, user’s information pack and installer’s hardware pack.
Assemble the wall plate cross member to the pre-plumbing
manifold as shown in Fig. 14 using the two M4 thread forming
screws supplied in the hardware pack.
Check that the position chosen for the appliance is in accordance
with the instructions given in Sections 4 and 5.
Hold the wall plate to the wall. Check that the plate is horizontal.
See Fig. 14.
Leave the pre-fitted plastic cover in place to protect the valves
and ‘O’ rings from dust and dirt during installation.
Mark the position of the fixing holes and the position of the flue
hole centre line onto the wall. Draw a horizontal line along the
top of the wall plate cross member as shown in Fig. 14.

Rear Flue –

Mark a vertical line through the flue hole centre point.

Measure upwards 800mm from the horizontal line and mark the
point. This is the centre point of the flue duct hole. See Fig. 16.

Side Flue

– Extend the horizontal line from Fig. 14 along the

appropriate wall. Check that it remains horizontal and measure
800mm upwards and mark a horizontal line. Measure 197mm
from the junction of the walls and mark a vertical line which will
then give the position of the flue hole.
Drill the six fixing holes 60mm deep for No. 12 size plugs. Cut
the flue duct hole at 110mm diameter (150mm dia. for internal
fitting). Ensure that the hole is horizontal through the wall.
Fix the wall plate and check that it is horizontal before tightening
the six screws.
Connect the gas, water and pressure relief valve connections to
the manifold. The primary system should be flushed and treated
in accordance with the recommendations of BS 7593:1992.
Remove the plastic cover from the manifold, and make sure that
the “O” rings are fitted clean and lubricated.
Slide the appliance onto the pre-plumbing manifold ensuring
that the three pegs are located correctly. Secure with the two M6
nuts and washers at the top and screw the appliance to the
manifold at the bottom, using the three retaining caps and M6
bolts. See Fig. 15.
Access to these pegs and caps can be made easier by removing
the bottom panel.
Unscrew the automatic air vent cap. See Fig. 16.
If the air and flue duct assembly is to be fitted from inside the
room then the ducts must be cut to length, assembled and
inserted through the wall at this stage before fitting the flue
elbow to the appliance. Refer to Section 11.3 following for the
assembly of the air and flue ducts.
Remove the fan. See Section 14.3(e).

11.3 AIR AND FLUE DUCT PREPARATION AND ASSEMBLY

Check the contents of the standard flue duct kit against the
packing list. Similarly check the extension duct kits if applicable.
Remove all the packing from the ducts and terminal assembly.
The standard flue kit accommodates a flue assembly up to
650mm long measured from the appliance casing to the outer
wall face. See dimension L, Figs.17 and 18. When dimension L is
greater than 650mm extension flue assemblies will be required.
Measure and cut the air and flue ducts to length ensuring that
the cuts are square and free from burrs. Always check the
dimensions before cutting the ducts.
Fit the restrictor ring in the flue terminal only when the overall
length of the flue is less than 1000mm and no additional flue
bends have been fitted.

11.4 EXTERNAL FITTING OF THE DUCT ASSEMBLY

Rear Flue Assembly

Measure distance L. See Fig. 17.
Air duct length = L + 146mm.
Flue duct length = L + 181mm.
Do not cut the drilled end of either duct.
Assemble the air and flue ducts to the terminal. Drill through the
holes in the terminal into the air duct and fix using the screws
provided. See Fig. 22. Join the extension ducts to the standard
ducts as indicated in Fig. 20, making sure the seal is in place.
Drill and screw together the air ducts.
From outside, push the assembly through the wall and enter the
ducts into the flue outlet turret.
Pull back the air duct slightly to allow access to the flue duct.
Drill through the flue duct and fix with the screws provided. Push
the air duct into the turret. Drill and fix the air duct to the turret.
See Fig. 19.
Align the flue turret with the 4 holes on the appliance and screw
down. See Fig. 16.
Make good the internal and external brickwork or rendering.
Refit the fan. Do not use any sealant on the joint. Replace the
inner casing cover.

Side Flue Assembly

Measure distance L. See Fig. 18.
Air duct length = L + 175mm.
Flue duct length = L + 210mm.
Do not cut the drilled end of either duct.
Assemble the air and flue ducts to the terminal. Drill through the
holes in the terminal into the air duct and fix using the screws
provided. See Fig. 22. Join the extension ducts to the standard
ducts as indicated in Fig. 20, making sure the seal is in place.
Drill and screw together the air ducts.
From outside, push the assembly through the wall and enter the 

13

Fig. 17. Flue duct length (rear flue).

Fig. 18.

Flue duct length (side flue).

L

L

Make good

External
wall face

Rear face of appliance
and face of mounting
wall

10mm

Make good

External
wall face

Appliance side
panel

10mm

Summary of Contents for 28CDi RSF

Page 1: ...BOILER OUTPUT Automatic Modulating Control To Domestic Hot Water To Central Heating Minimum 9 0 kW 9 0 kW Maximum 28 0 kW 24 0 kW IMPORTANT THESE INSTRUCTIONS APPLY IN THE UK ONLY THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER OR AT THE GAS METER This appliance must be installed by a competent person in accordance with the Gas Safety Installation and Use Regulations 1994 Bosch Group ...

Page 2: ...ting load 2 3 The control circuit provides direct burner ignition A pilot is not used 2 4 PRINCIPAL APPLIANCE COMPONENTS See Fig 1 A low thermal capacity Gas to Water heat exchanger A Water to Water heat exchanger to provide domestic hot water Fully modulating controls in the central heating and domestic hot water modes of operation An expansion vessel pressure gauge and pressure relief valve A by...

Page 3: ...or where it would cause a hazard to the user A drain cock to BS 2879 must be fitted to the lowest point of the system For circuit design purposes it is important that due note is taken of the information given in Table 3 relating to the available pump head 2 12 SHOWERS BIDETS TAPS AND MIXING VALVES Hot and cold taps and mixing valves used in the system must be suitable for operating at mains press...

Page 4: ...INIMUM COLD SUPPLY PRESSURE working for max hot water flow 1 2 bar MINIMUM COLD SUPPLY PRESSURE working to operate appliance 0 7 bar MAXIMUM CENTRAL HEATING FLOW TEMPERATURE Nominally 82 C 180 F OUTPUT TO DOMESTIC HOT WATER Modulating 9 0 to 28 kW OUTPUT TO CENTRAL HEATING Modulating 9 0 to 24 kW MAXIMUM DOMESTIC HOT WATER FLOW RATE from the appliance Nominally 10 litres min EQUIVALENT DOMESTIC HO...

Page 5: ...upply are maintained 4 7 The airing space must be separated from the boiler space by a perforated non combustible partition Expanded metal or rigid wire mesh are acceptable provided that the major dimension is less than 13mm See BS 6798 1987 4 8 No combustible surface must be within 75mm of the casing See BS476 4 4 9 The distance between the inner face of a cupboard door and the cabinet front shou...

Page 6: ...are given in Section 4 Siting The Appliance then permanent air vents for cooling are required One at high level and one at low level either direct to outside air or to a room Both vents must pass to the same room or be on the same wall to the outside air 6 4 The minimum free areas required are given below 6 5 Refer to BS 6798 and BS 5440 2 for additional information 6 Air Supply 5 Siting The Flue ...

Page 7: ...rey knob anti clockwise to allow water ingress and fill until the required pressure is reached Turn the grey knob clockwise to stop filling and remove the filling key by lining up the bayonet end of the key with the cutouts in the filling loop housing and withdrawing the key N B The key must always be removed from the filling loop housing after the system has been filled to prevent accidental fill...

Page 8: ...mer weather 9 8 It is suggested that long pipe runs to the taps or shower should be insulated to prevent the rapid cooling of domestic hot water after a tap or shower has been turned off 9 9 Hot and cold taps and mixing valves used with this appliance must be suitable for operating at mains pressure and temperatures of 65 C 9 10 No anti syphonage arrangements are necessary except for some loose he...

Page 9: ... Figs 11 12 and 13 The devices must be suitable for use with mains voltage 10 8 Facia mounted programmers are available as optional extras Instructions are supplied with the programmer kits 10 9 A time switch or programmer can be fitted externally to the appliance 10 10 The boiler is fitted with an internal frost thermostat which will protect the boiler from frost damage as long as the mains switc...

Page 10: ...ectronics Electronics Electronics Electronics Inputs Outputs Spark Indicators Settings Regulator valve CH demand indicator Red Spark electrodes DHW demand indicator Red Flame detect indicator Red Main valve Main valve Flow switch CH sensor DHW sensor Air pressure switch Flame sense Overheat cut off 24V programmer Reset button Gas valve mode switch CH pressure adjust pot CH Control knob DHW control...

Page 11: ...and programmer connections Fig 12 230 V programmer connections NS LS ST8 ST8 ST8 Remove link Neutral Live Switched live Neutral Neutral S w i t c h e d l i v e L i v e Live S w i t c h e d l i v e LR Spare NS LS LR Spare Spare Motor Neutral Live Switched live NS LS LR Motor ...

Page 12: ...andard flue duct 7 Restrictor ring 8 Flue terminal 9 Extension air duct 10 Extension flue duct 11 Flue duct sealing ring 12 In line flue elbow 13 Vertical flue adaptor IMPORTANT The restrictor ring must not be used for flue lengths over 650mm The flue must be installed as specified in BS 5440 Part 1 11 Installation 12 Fig 15 Fixing the appliance to the wall mounting plate Fig 16 Flue turret fixing...

Page 13: ... at this stage before fitting the flue elbow to the appliance Refer to Section 11 3 following for the assembly of the air and flue ducts Remove the fan See Section 14 3 e 11 3 AIR AND FLUE DUCT PREPARATION AND ASSEMBLY Check the contents of the standard flue duct kit against the packing list Similarly check the extension duct kits if applicable Remove all the packing from the ducts and terminal as...

Page 14: ...e the flue centering ring onto the air duct and tighten the screw See Fig 22 Fix the ducts and terminal assembly to the flue turret as described in Section 11 4 preceding Push the assembly through the wall so that the gasket flange is against the outside face of the wall See Fig 22 14 Fig 22 Duct and terminal assembly for internal fitting of the flue Fig 21 Terminal assembly for internal fitting o...

Page 15: ...water and gas connections have been tightened If a facia mounted programmer is to be fitted follow instructions with the programmer Hinge down the facia as described in Section 14 3 c Connect the mains electrical supply to the appliance at terminal ST 12 See Fig 8 Connect any room and or frost thermostats The electrical leads must pass through the appropriate space in the control panel and be fixe...

Page 16: ...ent to a static head of 5 metres 17 ft The charge pressure must not be less than the static head at the point of connection See Fig 7 A Schraeder type tyre valve is fitted to the expansion vessel to allow the charge pressure to be increased if necessary Set the System Pressure Remove the bottom panel to gain access to the filling loop assembly Insert the bayonet end of the filling key into the cor...

Page 17: ... the appliance has cooled to a pre set temperature Set the operating switch to OFF Central Heating Set the mode switch to the normal position Check that all the radiator valves are open Set the room thermostat and the Central Heating Temperature Control to maximum On sealed systems check that the system is pressurised and set to the required pressure as indicated on the gauge Set the Operating Swi...

Page 18: ...beintothemeasurementgapuptoadepthof50mm Seal any gaps Expected measurements should be between CO 0 001 and 0 003 CO2 6 7 and 7 0 After taking the measurement Replace and tighten the sealing screw Turn the Mode Switch back to the normal position Put the facia back in to the correct position IMPORTANT Disconnect the electrical supply at the mains and turn off the gas supply at the gas service cock o...

Page 19: ...ectricity and gas supplies before replacing any components After the replacement of any components check for gas soundness where relevant and carry out functional checks as described in Section 12 Commissioning 15 2 COMPONENT ACCESS To replace components it is necessary to remove one or more sections of the cabinet and cover plates within the appliance as described in Section 14 3 The facia panel ...

Page 20: ...aking care not to damage the electrode leads 9 Burner Injector See Fig 29 Remove the burner as described in Section 14 3 h Unscrew the brass injector from the burner Fit the replacement injector in the reverse order 10 Spark Electrode Assembly See Fig 29 Remove the combustion chamber front and sides as described in 14 3 g Carefully pull off the two electrode leads Undo the M4 extended nut and remo...

Page 21: ...as described in Sections 15 3 a and b Hinge down the facia assembly in the servicing position as described in Section 14 3 c Remove the Bottom panel water to water heat exchanger micro switch assembly and filling loop as described in Section 14 3 d and 15 4 20 and 24 Undo all the water connections to the valve Fit the replacement valve in the reverse order ensuring that the filter and all fibre wa...

Page 22: ... Grundfoss Ref 50 50 6500 1 8 716 143 108 0 25 173 001 Expansion Vessel Zilmet Ref 301010 1 8 716 142 514 0 42 E00 711 Water to Water Heat Exchanger Giannoni Ref PVW 14 E 1 8 716 142 903 0 34 173 005 Diverter Valve Giannoni Ref V37 OM I F 4 A spec D2109 1 8 716 156 746 0 104 394 291 DHW Flow Restrictor Type E 10 litre 1 8 716 141 057 0 105 Domestic Water Filter MPM V3326 1 8 716 148 400 0 109 E01 ...

Page 23: ...23 109 ...

Page 24: ...17 Operational Flow Diagrams 24 ...

Page 25: ...25 ...

Page 26: ...26 ...

Page 27: ... which represents the light situation during your fault Then refer to the appropriate following section This fault finding system assumes that the appliance has been operating correctly until the time of failure PRELIMINARY CHECKS Preliminary electrical system checks are the first electrical checks to be carried out during a fault finding procedure On completion of the Service Fault Finding task w...

Page 28: ...28 ...

Page 29: ...29 ...

Page 30: ...30 ...

Page 31: ...31 ...

Page 32: ...32 ...

Page 33: ...33 ...

Page 34: ...34 ...

Page 35: ...35 ...

Page 36: ...anged in the interests of continued improvement All goods sold are subject to our official Conditions of Sale a copy of which may be obtained on application PUBLICATION 8 716 145 020d 02 20 Bosch Group Worcester Heat Systems Limited Cotswold Way Warndon Worcester WR4 9SW Telephone 01905 754624 Fax 01905 754619 Technical Helpline 0990 266241 ...

Reviews: