background image

AIR PRESSURE SWITCH
2. Air Flow Pressure Switch.

See  Fig. 30.

Check that the electricity supply to the appliance is turned off.
Remove the cabinet front panel as described in Section 14.3 (a).
Carefully pull off the sensing tubes and the electrical connections
from the switch.
Unscrew the two screws underneath the gas valve and remove
the switch and bracket from the appliance.
Fit the replacement switch in the reverse order ensuring that the
electrical connections have been made to the correct terminals
on the switch. Check that the sensing tubes are fitted correctly.

3. Fan.

See Fig. 28.

Check that the electricity supply to the appliance is turned off.
Remove the fan assembly as described in Section 14.3(e).
Fit the replacement fan in the reverse order.
Black wire to terminal No. 1. Red wire to terminal No. 3. White
wire to terminal No. 4.

4. Overheat Thermostat. 

See Fig. 31.

Check that the electricity supply to the appliance is turned off.
Remove the inner casing cover as described in Section 14.3 (b).
Carefully pull off the two wires from the thermostat head.
Undo the two M3 screws and remove from the appliance.
Fit the replacement thermostat in the reverse order ensuring that

some heat sink compound is between the thermostat and the
plate.

5. Gas to Water Heat Exchanger.

See Fig. 31.

Check that the electricity supply to the appliance is turned off.
Drain the central heating circuit as described in Section 15.3 (a).
Remove the inner casing cover, fan, flue hood assembly, overheat
thermostat, central heating sensor, burner and automatic air
vent assembly as described  in Sections 14.3 (b, e, f, g and h),
15.4 (1), 15.4 (4) and 15.4 (13).
Slacken the two screws to remove the two retaining brackets and
lift the heat exchanger from the casing.
Fit the replacement heat exchanger in the reverse order ensuring
that both the “O” rings are correctly fitted and lubricated and a
layer of heat sink compound is on both the thermostats.
Open the valves and fill and re-pressurise the system as
described in Section 12.2.

7. Combustion Chamber Insulation.

Check that the electricity supply to the appliance is turned off.
Drain the central heating circuit as described in Section 15.3(a).
Remove the inner casing cover, fan, flue hood assembly, burner,
and Gas to Water heat exchanger as described in Sections 14.3
(b, e and f), and 15.4 (5). Remove the fibre insulation pads from
the combustion chamber side, rear, and front sections.
Fit the replacement pads in the reverse order taking care not to

damage them.
Open the valves and fill and re-pressurise the system as
described in Section 12.2.

8. Burner.

Check that the electricity and gas supplies to the appliance are
turned off.
Remove the burner assembly as described in Section 14.3 (h).
Fit the replacement burner in the reverse order taking care not to
damage the electrode leads.

9. Burner Injector. 

See Fig. 29.

Remove the burner as described in Section 14.3 (h).
Unscrew the brass injector from the burner.
Fit the replacement injector in the reverse order.

10. Spark Electrode Assembly.

See Fig. 29.

Remove the combustion chamber front and sides as described in
14.3 (g)
Carefully pull off the two electrode leads,
Undo the M4 extended nut and remove the spark electrode
assembly from the burner.
Fit the replacement electrode in the reverse order, checking that
the spark gap is 3 to 4mm.

11. Flame Sensor.

See Fig. 29.

Remove the burner as described in sections 14.3(h) and 15.4(8).
Undo the M3 screw and remove the sense electrode from the
burner.
Fit the replacement electrode in the reverse order, checking that
the sense gap is 5 to 6mm.

12. Gas Valve.

See Fig. 25.

Check that the electricity and gas supplies to the appliance are
turned off.
Hinge down the control box assembly in the servicing position
as described in Section 14.3(d).
Undo the two G

3

4

inch nuts on the gas valve and the two M4

screws on the gas valve bracket and remove the valve from the
appliance.
Whilst supporting the valve carefully pull off the three electrical
solenoid plug connections.
Fit the replacement gas valve in the reverse order ensuring the
sealing washers are correctly fitted.
Turn on the gas supply and check for soundness.

To set the burner pressure.

See Fig. 25.

After a new gas valve has been fitted the burner pressures must
be set.
Follow the procedure described in Section 12.4 – Appliance
Operation.
Turn both the central heating control knob and the domestic
water control knob to their maximum position (i.e. fully
clockwise).
The maximum domestic hot water burner pressure must be set
first as it effects the other pressures.
Turn the gas valve mode switch to the maximum position and
open a hot water tap.
Adjust the maximum pressure adjustment screw on the gas
valve to give a burner pressure of 12.1 mbar for natural gas
(G20).
For propane (G31) the maximum pressure adjustment screw
should be fully screwed in to give a pressure of 35.5 mbar.
Close the hot water tap and turn the gas valve mode switch to
the minimum position.
Adjust the start pressure adjustment screw on the gas valve to
give a burner pressure of 1.0 mbar for natural gas (G20) or 3.8
mbar for propane (G31).
Turn the gas valve mode switch to the normal position.
Ensure the appliance lights in the central heating mode.
Turn the CH pressure adjuster fully clockwise, wait until the
burner pressure has stopped increasing and then slowly turn the
CH pressure adjuster anti-clockwise until the burner pressure is
8.8 mbar for natural gas (G20) or 24.3 mbar for propane (G31).
After completing the adjustments, check the pressure settings
and re-adjust as necessary.

20

Fig. 31. Gas to water heat exchanger.

Auto air vent

Gas to water heat

exchanger

Retaining
clips

Retaining
bracket (2)

Retaining
screws (2)

Overheat
thermostat

Retaining
screws (2)

C.H.
sensor

Summary of Contents for 28CDi RSF

Page 1: ...BOILER OUTPUT Automatic Modulating Control To Domestic Hot Water To Central Heating Minimum 9 0 kW 9 0 kW Maximum 28 0 kW 24 0 kW IMPORTANT THESE INSTRUCTIONS APPLY IN THE UK ONLY THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER OR AT THE GAS METER This appliance must be installed by a competent person in accordance with the Gas Safety Installation and Use Regulations 1994 Bosch Group ...

Page 2: ...ting load 2 3 The control circuit provides direct burner ignition A pilot is not used 2 4 PRINCIPAL APPLIANCE COMPONENTS See Fig 1 A low thermal capacity Gas to Water heat exchanger A Water to Water heat exchanger to provide domestic hot water Fully modulating controls in the central heating and domestic hot water modes of operation An expansion vessel pressure gauge and pressure relief valve A by...

Page 3: ...or where it would cause a hazard to the user A drain cock to BS 2879 must be fitted to the lowest point of the system For circuit design purposes it is important that due note is taken of the information given in Table 3 relating to the available pump head 2 12 SHOWERS BIDETS TAPS AND MIXING VALVES Hot and cold taps and mixing valves used in the system must be suitable for operating at mains press...

Page 4: ...INIMUM COLD SUPPLY PRESSURE working for max hot water flow 1 2 bar MINIMUM COLD SUPPLY PRESSURE working to operate appliance 0 7 bar MAXIMUM CENTRAL HEATING FLOW TEMPERATURE Nominally 82 C 180 F OUTPUT TO DOMESTIC HOT WATER Modulating 9 0 to 28 kW OUTPUT TO CENTRAL HEATING Modulating 9 0 to 24 kW MAXIMUM DOMESTIC HOT WATER FLOW RATE from the appliance Nominally 10 litres min EQUIVALENT DOMESTIC HO...

Page 5: ...upply are maintained 4 7 The airing space must be separated from the boiler space by a perforated non combustible partition Expanded metal or rigid wire mesh are acceptable provided that the major dimension is less than 13mm See BS 6798 1987 4 8 No combustible surface must be within 75mm of the casing See BS476 4 4 9 The distance between the inner face of a cupboard door and the cabinet front shou...

Page 6: ...are given in Section 4 Siting The Appliance then permanent air vents for cooling are required One at high level and one at low level either direct to outside air or to a room Both vents must pass to the same room or be on the same wall to the outside air 6 4 The minimum free areas required are given below 6 5 Refer to BS 6798 and BS 5440 2 for additional information 6 Air Supply 5 Siting The Flue ...

Page 7: ...rey knob anti clockwise to allow water ingress and fill until the required pressure is reached Turn the grey knob clockwise to stop filling and remove the filling key by lining up the bayonet end of the key with the cutouts in the filling loop housing and withdrawing the key N B The key must always be removed from the filling loop housing after the system has been filled to prevent accidental fill...

Page 8: ...mer weather 9 8 It is suggested that long pipe runs to the taps or shower should be insulated to prevent the rapid cooling of domestic hot water after a tap or shower has been turned off 9 9 Hot and cold taps and mixing valves used with this appliance must be suitable for operating at mains pressure and temperatures of 65 C 9 10 No anti syphonage arrangements are necessary except for some loose he...

Page 9: ... Figs 11 12 and 13 The devices must be suitable for use with mains voltage 10 8 Facia mounted programmers are available as optional extras Instructions are supplied with the programmer kits 10 9 A time switch or programmer can be fitted externally to the appliance 10 10 The boiler is fitted with an internal frost thermostat which will protect the boiler from frost damage as long as the mains switc...

Page 10: ...ectronics Electronics Electronics Electronics Inputs Outputs Spark Indicators Settings Regulator valve CH demand indicator Red Spark electrodes DHW demand indicator Red Flame detect indicator Red Main valve Main valve Flow switch CH sensor DHW sensor Air pressure switch Flame sense Overheat cut off 24V programmer Reset button Gas valve mode switch CH pressure adjust pot CH Control knob DHW control...

Page 11: ...and programmer connections Fig 12 230 V programmer connections NS LS ST8 ST8 ST8 Remove link Neutral Live Switched live Neutral Neutral S w i t c h e d l i v e L i v e Live S w i t c h e d l i v e LR Spare NS LS LR Spare Spare Motor Neutral Live Switched live NS LS LR Motor ...

Page 12: ...andard flue duct 7 Restrictor ring 8 Flue terminal 9 Extension air duct 10 Extension flue duct 11 Flue duct sealing ring 12 In line flue elbow 13 Vertical flue adaptor IMPORTANT The restrictor ring must not be used for flue lengths over 650mm The flue must be installed as specified in BS 5440 Part 1 11 Installation 12 Fig 15 Fixing the appliance to the wall mounting plate Fig 16 Flue turret fixing...

Page 13: ... at this stage before fitting the flue elbow to the appliance Refer to Section 11 3 following for the assembly of the air and flue ducts Remove the fan See Section 14 3 e 11 3 AIR AND FLUE DUCT PREPARATION AND ASSEMBLY Check the contents of the standard flue duct kit against the packing list Similarly check the extension duct kits if applicable Remove all the packing from the ducts and terminal as...

Page 14: ...e the flue centering ring onto the air duct and tighten the screw See Fig 22 Fix the ducts and terminal assembly to the flue turret as described in Section 11 4 preceding Push the assembly through the wall so that the gasket flange is against the outside face of the wall See Fig 22 14 Fig 22 Duct and terminal assembly for internal fitting of the flue Fig 21 Terminal assembly for internal fitting o...

Page 15: ...water and gas connections have been tightened If a facia mounted programmer is to be fitted follow instructions with the programmer Hinge down the facia as described in Section 14 3 c Connect the mains electrical supply to the appliance at terminal ST 12 See Fig 8 Connect any room and or frost thermostats The electrical leads must pass through the appropriate space in the control panel and be fixe...

Page 16: ...ent to a static head of 5 metres 17 ft The charge pressure must not be less than the static head at the point of connection See Fig 7 A Schraeder type tyre valve is fitted to the expansion vessel to allow the charge pressure to be increased if necessary Set the System Pressure Remove the bottom panel to gain access to the filling loop assembly Insert the bayonet end of the filling key into the cor...

Page 17: ... the appliance has cooled to a pre set temperature Set the operating switch to OFF Central Heating Set the mode switch to the normal position Check that all the radiator valves are open Set the room thermostat and the Central Heating Temperature Control to maximum On sealed systems check that the system is pressurised and set to the required pressure as indicated on the gauge Set the Operating Swi...

Page 18: ...beintothemeasurementgapuptoadepthof50mm Seal any gaps Expected measurements should be between CO 0 001 and 0 003 CO2 6 7 and 7 0 After taking the measurement Replace and tighten the sealing screw Turn the Mode Switch back to the normal position Put the facia back in to the correct position IMPORTANT Disconnect the electrical supply at the mains and turn off the gas supply at the gas service cock o...

Page 19: ...ectricity and gas supplies before replacing any components After the replacement of any components check for gas soundness where relevant and carry out functional checks as described in Section 12 Commissioning 15 2 COMPONENT ACCESS To replace components it is necessary to remove one or more sections of the cabinet and cover plates within the appliance as described in Section 14 3 The facia panel ...

Page 20: ...aking care not to damage the electrode leads 9 Burner Injector See Fig 29 Remove the burner as described in Section 14 3 h Unscrew the brass injector from the burner Fit the replacement injector in the reverse order 10 Spark Electrode Assembly See Fig 29 Remove the combustion chamber front and sides as described in 14 3 g Carefully pull off the two electrode leads Undo the M4 extended nut and remo...

Page 21: ...as described in Sections 15 3 a and b Hinge down the facia assembly in the servicing position as described in Section 14 3 c Remove the Bottom panel water to water heat exchanger micro switch assembly and filling loop as described in Section 14 3 d and 15 4 20 and 24 Undo all the water connections to the valve Fit the replacement valve in the reverse order ensuring that the filter and all fibre wa...

Page 22: ... Grundfoss Ref 50 50 6500 1 8 716 143 108 0 25 173 001 Expansion Vessel Zilmet Ref 301010 1 8 716 142 514 0 42 E00 711 Water to Water Heat Exchanger Giannoni Ref PVW 14 E 1 8 716 142 903 0 34 173 005 Diverter Valve Giannoni Ref V37 OM I F 4 A spec D2109 1 8 716 156 746 0 104 394 291 DHW Flow Restrictor Type E 10 litre 1 8 716 141 057 0 105 Domestic Water Filter MPM V3326 1 8 716 148 400 0 109 E01 ...

Page 23: ...23 109 ...

Page 24: ...17 Operational Flow Diagrams 24 ...

Page 25: ...25 ...

Page 26: ...26 ...

Page 27: ... which represents the light situation during your fault Then refer to the appropriate following section This fault finding system assumes that the appliance has been operating correctly until the time of failure PRELIMINARY CHECKS Preliminary electrical system checks are the first electrical checks to be carried out during a fault finding procedure On completion of the Service Fault Finding task w...

Page 28: ...28 ...

Page 29: ...29 ...

Page 30: ...30 ...

Page 31: ...31 ...

Page 32: ...32 ...

Page 33: ...33 ...

Page 34: ...34 ...

Page 35: ...35 ...

Page 36: ...anged in the interests of continued improvement All goods sold are subject to our official Conditions of Sale a copy of which may be obtained on application PUBLICATION 8 716 145 020d 02 20 Bosch Group Worcester Heat Systems Limited Cotswold Way Warndon Worcester WR4 9SW Telephone 01905 754624 Fax 01905 754619 Technical Helpline 0990 266241 ...

Reviews: