background image

The boiler requires 3.35 m

3

/h (115 ft

3

/hr) of natural (G20) or 1.29

m

3

/hr (46 ft

3

/hr or propane gas (G31). The gas meter and supply

pipes must be capable of supplying this quantity of gas in
addition to the demands of any other appliances being served.
The meter governor should deliver a dynamic pressure of 20
mbar (8in wg.) for natural gas or 37 mbar (14.4 in wg.) for
propane.
The complete installation, including the gas meter, must be
tested for soundness and purged. Refer to BS 6891.

2.7 PACKING

The appliance and flue components are packed in separate
cartons.

2.8 GENERAL INSTALLATION

The appliance is for connection to a sealed or open vented
primary system.
The specified ventilation openings made into a wall or
compartment door must not be obstructed.
If the appliance is to be fitted into a compartment then the
compartment must conform to the requirements of
BS

.

5440:2:1989.

Notwithstanding the instructions given in BS

.

5440:2:1989, this

appliance may be fitted in a compartment with no vents as long
as the minimum clearances stated in Section 6: Air Supply, are
maintained.
Do not place anything on top of the appliance.
The clearances specified for servicing must be maintained.

2.9 FLUE

The appliance has a multi-directional horizontal fanned flue
system.
The standard flue assembly length is from 100mm to 650mm.
Extension flue lengths available are from 651mm to 3000mm.
A terminal guard, Type K2, GC 393 553, is available from Tower
Flue Components, Vale Rise, Tonbridge,TN9 1TB.
Do not allow the flue terminal fitted to the outside wall to
become obstructed or damaged.
A kit for internal fixing of the flue is available separately.

2.10 CONTROLS

The electronic control system and gas valve modulate the heat
input in response to the central heating and domestic hot water
temperature settings between minimum and maximum.
The ON/OFF switch will turn the mains electricity on and off to
the appliance.
The Central Heating Temperature control knob provides for the
selection of domestic hot water only (Turned fully anti-clockwise)
or central heating and domestic hot water (Turned clockwise).
Facia mounted programmers are available as an optional extra.
A remote mounted programmer may be connected to the
appliance.
The integral facia displays indicate the status of the appliance.
There is provision for the connection of a mains voltage room
thermostat and/or a frost thermostat.
The electronic controls prevent rapid cycling of the appliance in
the central heating mode.

2.11 SYSTEM NOTES
IMPORTANT

Check that no dirt is left in either the gas or water pipework as
this could cause damage to the appliance. Thoroughly flush the
heating system and the cold water mains supply in accordance
with the recommendations of BS7593: 1992 
Purge the gas supply before finally connecting the appliance.
The water pipe connections throughout a sealed system must be
capable of sustaining a pressure of up to 3 bar.
Radiator valves must conform to the requirements of BS 2767 1991.
The relief valve discharge must be directed away from any electrical
components or where it would cause a hazard to the user.
A drain cock to BS 2879 must be fitted to the lowest point of the
system.

For circuit design purposes it is important that due note is taken of
the information given in Table 3 relating to the available pump head.

2.12 SHOWERS, BIDETS, TAPS AND MIXING VALVES

Hot and cold taps and mixing valves used in the system must be
suitable for operating at mains pressure.
Thermostatically controlled shower valves will guard against the
flow of water at too high a temperature.
If using a pressure equalising valve, set the Domestic Hot Water
temperature control knob to the ‘MAX’ position.
Hot and cold mains fed water can be supplied direct to an over-
rim flushing bidet subject to local Water Company requirements.
With all mains fed systems the flow of water from the individual
taps will vary with the number of outlets operated
simultaneously and the cold water mains supply pressure to the
property. Flow balancing using ‘Ball-o-Fix’ type valves is
recommended to avoid an excessive reduction in flow to
individual outlets. For further information contact Worcester
Heat Systems Ltd.

2.13 SAFETY CONSIDERATIONS

The appliance must not be operated in a waterless condition.
The appliance must not be operated with the boiler inner casing
cover removed.
Work must not be carried out on the appliance without the gas
and electricity supplies being switched off.
Checks must be made to ensure that the ventilation openings
made into walls and partitions are of the correct size and are not
obstructed.

2.14 OPERATION
Domestic Hot Water:

With a demand for hot water the burner

will light at its maximum setting and then automatically adjust
its output to maintain the temperature of the delivered water.
When hot water is no longer required, the burner will extinguish.
The fan and pump may continue to run for a short period to
dissipate the residual heat from the appliance.

Central Heating:

With a demand for heating the burner will light

at its minimum setting and gradually increase to give the
maximum output. The output of the appliance is then
automatically adjusted to maintain the temperature of the
system. The output can reduce down to a minimum of 9.0 kW. If
the system no longer requires even the minimum output to
maintain the desired room temperature the burner will
extinguish. The fan and pump may continue to run to dissipate
the residual heat from the appliance. The appliance will remain
off for a fixed period of three minutes before re-lighting to
automatically meet the system requirements.

Domestic Hot Water and Central Heating:

The appliance will

supply heat to the central heating system as required. A demand
for domestic hot water at a tap or shower will override the
central heating requirement for the period of the domestic hot
water demand. When hot water is no longer required the
appliance will return to the central heating state and its normal
mode of operation. The fan may continue to run to dissipate the
residual heat from the appliance as necessary.

3

Fig. 1a.

IMPORTANT:

After flushing out all
pipework and before
mounting the appliance
please ensure that the
water inlet filter contained
in the fixing kit is fitted as
shown.

Inlet water
filter

Cold water
inlet on
diverter valve

Summary of Contents for 28CDi RSF

Page 1: ...BOILER OUTPUT Automatic Modulating Control To Domestic Hot Water To Central Heating Minimum 9 0 kW 9 0 kW Maximum 28 0 kW 24 0 kW IMPORTANT THESE INSTRUCTIONS APPLY IN THE UK ONLY THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER OR AT THE GAS METER This appliance must be installed by a competent person in accordance with the Gas Safety Installation and Use Regulations 1994 Bosch Group ...

Page 2: ...ting load 2 3 The control circuit provides direct burner ignition A pilot is not used 2 4 PRINCIPAL APPLIANCE COMPONENTS See Fig 1 A low thermal capacity Gas to Water heat exchanger A Water to Water heat exchanger to provide domestic hot water Fully modulating controls in the central heating and domestic hot water modes of operation An expansion vessel pressure gauge and pressure relief valve A by...

Page 3: ...or where it would cause a hazard to the user A drain cock to BS 2879 must be fitted to the lowest point of the system For circuit design purposes it is important that due note is taken of the information given in Table 3 relating to the available pump head 2 12 SHOWERS BIDETS TAPS AND MIXING VALVES Hot and cold taps and mixing valves used in the system must be suitable for operating at mains press...

Page 4: ...INIMUM COLD SUPPLY PRESSURE working for max hot water flow 1 2 bar MINIMUM COLD SUPPLY PRESSURE working to operate appliance 0 7 bar MAXIMUM CENTRAL HEATING FLOW TEMPERATURE Nominally 82 C 180 F OUTPUT TO DOMESTIC HOT WATER Modulating 9 0 to 28 kW OUTPUT TO CENTRAL HEATING Modulating 9 0 to 24 kW MAXIMUM DOMESTIC HOT WATER FLOW RATE from the appliance Nominally 10 litres min EQUIVALENT DOMESTIC HO...

Page 5: ...upply are maintained 4 7 The airing space must be separated from the boiler space by a perforated non combustible partition Expanded metal or rigid wire mesh are acceptable provided that the major dimension is less than 13mm See BS 6798 1987 4 8 No combustible surface must be within 75mm of the casing See BS476 4 4 9 The distance between the inner face of a cupboard door and the cabinet front shou...

Page 6: ...are given in Section 4 Siting The Appliance then permanent air vents for cooling are required One at high level and one at low level either direct to outside air or to a room Both vents must pass to the same room or be on the same wall to the outside air 6 4 The minimum free areas required are given below 6 5 Refer to BS 6798 and BS 5440 2 for additional information 6 Air Supply 5 Siting The Flue ...

Page 7: ...rey knob anti clockwise to allow water ingress and fill until the required pressure is reached Turn the grey knob clockwise to stop filling and remove the filling key by lining up the bayonet end of the key with the cutouts in the filling loop housing and withdrawing the key N B The key must always be removed from the filling loop housing after the system has been filled to prevent accidental fill...

Page 8: ...mer weather 9 8 It is suggested that long pipe runs to the taps or shower should be insulated to prevent the rapid cooling of domestic hot water after a tap or shower has been turned off 9 9 Hot and cold taps and mixing valves used with this appliance must be suitable for operating at mains pressure and temperatures of 65 C 9 10 No anti syphonage arrangements are necessary except for some loose he...

Page 9: ... Figs 11 12 and 13 The devices must be suitable for use with mains voltage 10 8 Facia mounted programmers are available as optional extras Instructions are supplied with the programmer kits 10 9 A time switch or programmer can be fitted externally to the appliance 10 10 The boiler is fitted with an internal frost thermostat which will protect the boiler from frost damage as long as the mains switc...

Page 10: ...ectronics Electronics Electronics Electronics Inputs Outputs Spark Indicators Settings Regulator valve CH demand indicator Red Spark electrodes DHW demand indicator Red Flame detect indicator Red Main valve Main valve Flow switch CH sensor DHW sensor Air pressure switch Flame sense Overheat cut off 24V programmer Reset button Gas valve mode switch CH pressure adjust pot CH Control knob DHW control...

Page 11: ...and programmer connections Fig 12 230 V programmer connections NS LS ST8 ST8 ST8 Remove link Neutral Live Switched live Neutral Neutral S w i t c h e d l i v e L i v e Live S w i t c h e d l i v e LR Spare NS LS LR Spare Spare Motor Neutral Live Switched live NS LS LR Motor ...

Page 12: ...andard flue duct 7 Restrictor ring 8 Flue terminal 9 Extension air duct 10 Extension flue duct 11 Flue duct sealing ring 12 In line flue elbow 13 Vertical flue adaptor IMPORTANT The restrictor ring must not be used for flue lengths over 650mm The flue must be installed as specified in BS 5440 Part 1 11 Installation 12 Fig 15 Fixing the appliance to the wall mounting plate Fig 16 Flue turret fixing...

Page 13: ... at this stage before fitting the flue elbow to the appliance Refer to Section 11 3 following for the assembly of the air and flue ducts Remove the fan See Section 14 3 e 11 3 AIR AND FLUE DUCT PREPARATION AND ASSEMBLY Check the contents of the standard flue duct kit against the packing list Similarly check the extension duct kits if applicable Remove all the packing from the ducts and terminal as...

Page 14: ...e the flue centering ring onto the air duct and tighten the screw See Fig 22 Fix the ducts and terminal assembly to the flue turret as described in Section 11 4 preceding Push the assembly through the wall so that the gasket flange is against the outside face of the wall See Fig 22 14 Fig 22 Duct and terminal assembly for internal fitting of the flue Fig 21 Terminal assembly for internal fitting o...

Page 15: ...water and gas connections have been tightened If a facia mounted programmer is to be fitted follow instructions with the programmer Hinge down the facia as described in Section 14 3 c Connect the mains electrical supply to the appliance at terminal ST 12 See Fig 8 Connect any room and or frost thermostats The electrical leads must pass through the appropriate space in the control panel and be fixe...

Page 16: ...ent to a static head of 5 metres 17 ft The charge pressure must not be less than the static head at the point of connection See Fig 7 A Schraeder type tyre valve is fitted to the expansion vessel to allow the charge pressure to be increased if necessary Set the System Pressure Remove the bottom panel to gain access to the filling loop assembly Insert the bayonet end of the filling key into the cor...

Page 17: ... the appliance has cooled to a pre set temperature Set the operating switch to OFF Central Heating Set the mode switch to the normal position Check that all the radiator valves are open Set the room thermostat and the Central Heating Temperature Control to maximum On sealed systems check that the system is pressurised and set to the required pressure as indicated on the gauge Set the Operating Swi...

Page 18: ...beintothemeasurementgapuptoadepthof50mm Seal any gaps Expected measurements should be between CO 0 001 and 0 003 CO2 6 7 and 7 0 After taking the measurement Replace and tighten the sealing screw Turn the Mode Switch back to the normal position Put the facia back in to the correct position IMPORTANT Disconnect the electrical supply at the mains and turn off the gas supply at the gas service cock o...

Page 19: ...ectricity and gas supplies before replacing any components After the replacement of any components check for gas soundness where relevant and carry out functional checks as described in Section 12 Commissioning 15 2 COMPONENT ACCESS To replace components it is necessary to remove one or more sections of the cabinet and cover plates within the appliance as described in Section 14 3 The facia panel ...

Page 20: ...aking care not to damage the electrode leads 9 Burner Injector See Fig 29 Remove the burner as described in Section 14 3 h Unscrew the brass injector from the burner Fit the replacement injector in the reverse order 10 Spark Electrode Assembly See Fig 29 Remove the combustion chamber front and sides as described in 14 3 g Carefully pull off the two electrode leads Undo the M4 extended nut and remo...

Page 21: ...as described in Sections 15 3 a and b Hinge down the facia assembly in the servicing position as described in Section 14 3 c Remove the Bottom panel water to water heat exchanger micro switch assembly and filling loop as described in Section 14 3 d and 15 4 20 and 24 Undo all the water connections to the valve Fit the replacement valve in the reverse order ensuring that the filter and all fibre wa...

Page 22: ... Grundfoss Ref 50 50 6500 1 8 716 143 108 0 25 173 001 Expansion Vessel Zilmet Ref 301010 1 8 716 142 514 0 42 E00 711 Water to Water Heat Exchanger Giannoni Ref PVW 14 E 1 8 716 142 903 0 34 173 005 Diverter Valve Giannoni Ref V37 OM I F 4 A spec D2109 1 8 716 156 746 0 104 394 291 DHW Flow Restrictor Type E 10 litre 1 8 716 141 057 0 105 Domestic Water Filter MPM V3326 1 8 716 148 400 0 109 E01 ...

Page 23: ...23 109 ...

Page 24: ...17 Operational Flow Diagrams 24 ...

Page 25: ...25 ...

Page 26: ...26 ...

Page 27: ... which represents the light situation during your fault Then refer to the appropriate following section This fault finding system assumes that the appliance has been operating correctly until the time of failure PRELIMINARY CHECKS Preliminary electrical system checks are the first electrical checks to be carried out during a fault finding procedure On completion of the Service Fault Finding task w...

Page 28: ...28 ...

Page 29: ...29 ...

Page 30: ...30 ...

Page 31: ...31 ...

Page 32: ...32 ...

Page 33: ...33 ...

Page 34: ...34 ...

Page 35: ...35 ...

Page 36: ...anged in the interests of continued improvement All goods sold are subject to our official Conditions of Sale a copy of which may be obtained on application PUBLICATION 8 716 145 020d 02 20 Bosch Group Worcester Heat Systems Limited Cotswold Way Warndon Worcester WR4 9SW Telephone 01905 754624 Fax 01905 754619 Technical Helpline 0990 266241 ...

Reviews: