Installation
39
Greenstar 4000 – 6 720 891 162 (2020/09)
5.4
Flue turret/adaptor installation
NOTICE
Flue installation
▶ Refer to the Flue Kit Installation instructions provided with your flue
kit to correctly install the flue with this appliance.
▶ Do not exceed the maximum straight length for a horizontal or vertical
flue or a 60mm plume management system (if used) as stated in
chapter 4.4
Telescopic flue
▶ Cutting the flue to an exact measurement is not required as the
telescopic flue terminal can allow for some adjustment.
Apply silicone lubricant to sealing surfaces, to ease assembly of flue
components.
Refer to the manual supplied with the flue kit for complete installation
instructions.
▶ For plume management and effective flue lengths (
chapter 4.4).
Additional notes and reminders:
• Ensure that all cut lengths are square and free from burrs and cutting/
filing debris.
• Ensure that the flue and seals are not damaged.
• The flue is sealed when assembled correctly, ensure the components
are pushed fully home and secured.
• The flue rises from the appliance at an angle of 3° or 52mm per metre
length.
• Support the flue at each flue extension joint and at each change of
direction, use suitable brackets and fittings:
– Flue bracket 100mm, part number: 7 716 191 177.
– Flue brackets 100mm x 6, part number: 7 716 191 178.
– Flue bracket 125mm, part number: 7 716 191 179.
• Ensure the external wall seal is fitted and properly located in the
groove provided on the terminal. This seal must be installed in the
groove unless the flue is extended beyond a gutter or balcony as
shown in the installation instructions.
Fig. 53 Slope for condensate disposal
Refer to figure 54.
▶ Remove the three inner flue tube retaining screws [1].
– The inner tube will be held in place in the appliance.
▶ Check the appliance flue seal [2] is correctly seated and apply
silicone grease.
Flue turret [A] fitting
▶ Align the flue turret [A] to the appliance flue outlet with flat facing [3]
to the rear of the appliance.
– This should be pushed straight down, on to the appliance.
▶ The three inner flue tube retaining screws [1] are re-used to secure
the flue turret [A].
Vertical adaptor [B] fitting
▶ Align the vertical adaptor [B] to the appliance flue outlet with flat
facing [3] to the rear of the appliance.
– This should be pushed straight down, on to the appliance.
▶ The three replacement retaining screws [4] supplied with the
adaptor kit are used to secure the vertical adaptor [B].
Fig. 54 Flue turret/adaptor connection
104mm
52mm
2,000mm
1,000mm
0010013472-001
0010023595-001
1
B
2
3
3
1
4
A