Fault finding and diagnosis
Greenstar 4000 – 6 720 891 162 (2020/09)
74
363
V
System fault boiler electronics / basic
controller
▶ Check and replace the ionisation cable.
▶ Check and replace the electrodes if required.
▶ Check and replace the control unit and/or burner control unit.
810
Hot water remains cold
▶ Reset the appliance and wait 24 hours
▶ Check the DHW valves,
▶ Check the 3-way valve, replace if necessary,
▶ Check that the tank is properly connected.
811
A
Hot water heating: thermal disinfection
failed
▶ If water is being drawn constantly, take action to stop this.
▶ Position the DHW temperature sensor correctly.
▶ Check that there is contact between the DHW cylinder temperature sensor and the
cylinder.
▶ Vent the cylinder circuit.
▶ Set DHW heating to "priority".
▶ Check plate heat exchanger for calcification.
▶ Check sizing of DHW circulation line and heat loss.
1010
–
No communication via EMS BUS
connection
▶ Check the grey ribbon on far right of the PCB (low voltage connection).
▶ If using a Key control product check the Key connections (black, white, red, green) are
plugged into the correct position on the PCB (under installer cover on the far right hand
side, leaving one space to the BUS connection).
▶ Check that the Key is pushed fully home.
▶ Check the batteries of the room control.
▶ Check the bridging links are fitted at LR & 230 V out.
▶ For wired room controls check the EMS BUS Voltage to the remote control is
12 - 15V DC.
▶ Check the 230 V external wiring does not run alongside the BUS connections, thus
causing interference.
▶ Replace the control unit
1013 W
Max. combustion point reached
The service reminder message is present due to the maximum burner hours service
threshold being reached.
▶ Carry out maintenance.
▶ Reset the maintenance code via the reset menu.
1017 W
System pressure too low
▶ Top up system water and vent the system.
▶ Check the voltage to the pressure sensor and the signal back from the pressure sensor.
▶ Replace the pressure sensor.
1018 W
Maintenance interval expired
▶ Carry out maintenance.
▶ Reset the maintenance code via the reset menu.
1019 W
Incorrect pump type detected
▶ Pump communication failure or wrong pump is fitted (i.e. non-ErP).
▶ Check the pump communication wire is connected and has continuity.
▶ Replace the pump for correct modulating pump.
1021 B
Cylinder charging or hot water temperature
sensor faulty
A 1021 error can only be cleared by powering the appliance off and back on again the hot
water sensor has been changed if open or short circuit, or refitted to the pipe if it has fallen
off.
▶ Check the domestic hot water temperature sensor is connected and the harness is
fitted securely to the sensor.
▶ Check the resistance of the temperature sensor and replace if required.
▶ Check the continuity of harness and replace if required.
1022 W
Cylinder temp. sensor faulty or contact
problems
▶ Connect the plug to the temperature sensor correctly.
▶ Connect the plug to the control device correctly.
▶ Check the temperature sensor, replace if necessary.
▶ Check temperature sensor connecting lead, replace if necessary.
1023 W
Maximum run time including standby time
reached
The service reminder message is present due to the maximum run time (boiler hours)
being reached.
▶ Carry out maintenance.
▶ Reset the maintenance code via the reset menu.
1037 W
Outside temp. sensor faulty - heating back-
up operation active
Tip: Check the weather compensation is applicable and the menu has not been
accidentally switched on in the menu.
▶ Check the positioning of the outside weather sensor.
▶ Check the weather sensor connections on the control board.