Commissioning
Worcester Commercial Boiler Series – 6720814332 (2019/04)
38
▶ Select the μA measurement value at the multi-meter.
▶ Bring the boiler into operation.
▶ Make sure that the boiler can dissipate the heat generated.
▶ Start the chimney sweep mode(
Chapter 7.3).
▶ Set the smallest possible output value in % (partial load).
▶ Measure the ionisation current.
The ionisation current must be at least 3 μA.
▶ If the value is lower, check the gas/air ratio and the monitoring
electrode.
▶ Enter the value in the maintenance protocol (
Chapter 11.15).
▶ Switch off the chimney sweep mode.
▶ Take the boiler out of operation.
▶ Remove the multi-meter.
▶ Re-connect the ionisation plugs.
▶ Bring the boiler into operation.
8.11
Testing for gas leaks
NOTICE:
Damage to the boiler due to short-circuit.
▶ When using leak detection spray, cover the plug and cables.
▶ Start the chimney sweep mode (
Chapter 7.3).
▶ As soon as the burner is on, check all gas-carrying components using
an approved gas leak detection spray.
▶ Check the rubber gasket [1] at the ignition unit and the monitoring
electrode for tightness.
Fig. 74 Inspecting the gas train
▶ Determine the cause of a possible leak.
▶ Take steps to remedy the leak.
▶ Exit the chimney sweep mode.
8.12
Check the operating characteristics of the boiler
▶ Create a heat demand and check whether the boiler starts burning
after several minutes to support the boiler operation.
▶ If applicable: open a DHW tap and check the DHW temperature and
DHW volume.
8.13
Final steps
▶ Fit the casing.
▶ Complete the Benchmark checklist (50-V2 and 65-V2) or
commissioning report (85-V2 and 100-V2).
▶ Place second ID sticker [1] (part of the documentation set) at the
bottom right on the front cover.
Fig. 75 Second ID sticker
8.14
Inform the user
▶ Familiarise the user with the heating system and operation of the
boiler.
▶ Explain to the user how the heating system must be filled.
▶ Point out to the user that they must not carry out conversions, repairs
or maintenance themselves.
▶ Fill out the commissioning report to confirm commissioning
(
Chapter 8.15).
▶ Hand the technical documentation to the user.
8.15
Commissioning report (for installations below
70 kW)
▶ Sign all completed commissioning work and enter the date.
0010010037-001
1
Commissioning steps
Page
Measured
values
Remarks
1.
Filling and venting the heating
system.
• Expansion vessel pre-
charge pressure (observe
the installation instructions
for the expansion vessel)
• Heating system fill pressure
_______bar
_______bar
2.
Check gas type against the data
plate.
3.
Vent the gas line.
4.
Check the combustion air/flue
gas connection.
5.
Adjusting the boiler:
• Adjust the output
• Adjust the flow temperature
• Setting pump run-on time
6.
Measure the gas supply
pressure.
7.
Measure gas/air ratio.
8.
Measure the CO
2
content.
9.
Check the gas tightness.
10. Check the flue gas tightness.
11. Check the function of the
boiler.
12. Fitting the casing.
13. Instruct the user, hand over
technical documentation.
Confirm professional commissioning:
Company stamp/
signature/date
0010026009-001
1