Display codes
49
Worcester Commercial Boiler Series – 6720814332 (2019/04)
Table 18 Operating and fault codes
3
The burner control unit or the KIM is faulty.
▶ Check the plug and wiring of the burner control unit.
▶ Check the operating characteristics of the boiler by replacing the
burner control unit.
3
The sensor test has failed.
▶ Check the cabling and plug of the sensors.
▶ Check the operating characteristics of the sensors. Replace the
faulty component if necessary.
The burner control unit or the KIM is faulty.
▶ Check the plug and wiring of the burner control unit.
▶ Check the operating characteristics of the boiler by replacing the
burner control unit.
3
The burner control unit is faulty.
The burner control unit or the KIM is faulty.
2
The burner control unit or the KIM is faulty.
3
An ionisation current was measured before the
burner started.
▶ Check the plug of the ionisation pin for damage and wear.
▶ Check the ignition device for damage and wear. Replace the faulty
component, with gaskets, if necessary.
2
A brief power failure has occurred.
▶ Check whether the fault may have been caused by the presence of a
power unit, a wind turbine or other equipment that could cause an
interruption.
▶ Check the electrical installation.
3
An ionisation current was measured after the
burner went out.
▶ Inspect the ionising part of the ignition device. Replace the faulty
component if necessary.
▶ Check whether the gas/air ratio upstream and downstream of the
burner phase remains the same.
▶ Check whether voltage is present at the gas valve once the burner
phase has expired.
▶ Check the operating characteristics of the boiler by replacing the
burner control unit.
3
The mains voltage was interrupted during an
interlocking fault.
▶ Reset the boiler.
3
The burner control unit or the KIM is faulty.
▶ Check plug and wiring of the burner control unit.
▶ Check the operating characteristics of the boiler by replacing the
burner control unit.
The current water pressure is too low. This limits
the performance in heating mode as well as DHW
mode.
▶ Vent the heating system and the boiler.
▶ Refill the heating system.
The boiler is reset.
The boiler is reset.
Code
Code
type
Designation
Remedy