Inspection and maintenance
59
Greenstar 4000 – 6 720 891 161 (2020/09)
▶ Re-check the fan pressure readings.
If the appliance, after completing the above checks, fails the fan
pressure test then contact Worcester, Bosch Group for advice.
▶ Switch the appliance off after completing pressure check.
▶ Disconnect the digital manometer and replace the test point cover.
8.4
Check working gas inlet pressure
NOTICE
Gas inlet pressure
▶ Do not continue with the other checks if the correct gas inlet pressure
can not be achieved at maximum output.
▶ Check the gas supply working pressures in the system conform to the
readings shown in the table shown in chapter 6.5 "Checking gas inlet
pressure".
8.5
Flue gas analysis
NOTICE
Combustion testing
▶ Combustion testing must be carried out by a competent person.
Testing must not be attempted unless the person carrying out the
combustion check is equipped with a calibrated flue gas analyser
conforming to BS 7967 and is competent in its use.
Flue gas analysis
▶ Ensure that the gas inlet pressure has been checked and is
satisfactory.
▶ Refit the test point plugs after the test has been completed.
▶ Set the appliance to maximum and minimum output in chimney
sweep mode (
6.4 "Chimney sweep mode") for the flue gas
analysis checks.
▶ Check that the readings conform to those given in the following
tables. In addition to CO and CO/CO
2
ratio checks also check the
maximum and minimum CO
2
percentage reading.
CO/CO
2
settings
Table 30 CO
2
settings
If the CO
2
is out of tolerance then please check:
▶ The gas inlet pressure.
▶ The gas rate.
▶ The fan test pressure.
▶ The flue and air intake, plus any possible blockages in the condensate
disposal.
▶ The condition of burner.
▶ For leaks or obstructions in the exhaust paths.
▶ That the injector is clean.
After all checks have been completed and the CO
2
is still out of tolerance
then contact Worcester, Bosch Group helpline 0330 123 3366 before
making any adjustment to the gas valve.
8.6
Checking the flue integrity
NOTICE
▶ Check flue joints are secure, the terminal and the terminal guard, if
fitted are clear and undamaged.
▶ Combustion testing must be carried out to BS 7967 by a competent
person. Testing must not be attempted unless the person carrying
out the combustion check is equipped with a calibrated Combustion
Analyser conforming to BS EN 50379 and is competent in its use.
Flue gas analysis
▶ Ensure that the gas inlet pressure has been checked and is
satisfactory.
▶ Refit the test point plugs after the test has been completed.
▶ Refer to chapter 6.9 "Checking flue integrity" and check that the
readings conform to those given, confirming flue system and
combustion circuit are ok.
8.7
Cleaning the siphon and heat exchanger
8.7.1
Checking the electrodes and cleaning the heat exchanger
CAUTION
Risk of burns due to hot surfaces!
Individual components of the appliance can become very hot even after
being shut down for a long time.
▶ Allow the appliance to cool down before carrying out any work.
▶ If necessary, wear protective gloves.
WARNING
Material damage due to hot flue gas! - Gaskets and seals - gas related
components
Hot flue gas can leak through defective gaskets, damage the appliance
and endanger safe operation.
▶ Burner/electrode assembly gasket must be replaced if disturbed.
▶ Other gaskets/seals must be checked and replaced where necessary.
▶ Do not attempt the cleaning procedure unless new gaskets and seals
are available.
▶ Ensure that the gaskets are positioned correctly.
NOTICE
Material damage due to chemicals
Using chemicals during the cleaning of the heat exchanger assembly and
associated parts or carrying out maintenance can damage the sealing
components. This can cause exhaust gas to escape during operation.
▶ Do not use chemicals to flush the heat exchanger assembly and
associated gas carrying components.
CO
2
Reading
CO Reading
Natural Gas appliances
Maximum rated Output
1)
1) Should be measured 10 minutes after firing the appliance
Between 9.0 and 9.8%
<250ppm
Minimum rated Output
1)
A minimum of 0.2 lower than the maximum reading
taken and between 8.2 and 9.0%
<250ppm
LPG appliances
Maximum rated Output
1)
Between 10.4 and 11.0%
<250ppm
Minimum rated Output
1)
A minimum of 0.2 lower than the maximum reading
taken and between 10.0 and 10.4%
<250ppm