FAULT FINDING & DIAGNOSIS
6 720 812 175 (2014/07)
51
7
FAULT FINDING & DIAGNOSIS
7.1
FAULT FINDING
The electronic control system for this boiler incorporates a blue central
indicator. This normally confirms the permanent mains supply but, by
flashing during a fault, provides a guide to the cause as listed.
This fault finding system assumes that the appliance has been operating
normally until the time of failure (i.e. not a first installation error).
PRELIMINARY CHECKS: Preliminary electrical system checks are the
first electrical checks to be carried out during a fault-finding procedure.
On completion of the Service/Fault-Finding task which has required the
breaking and remaking of electrical connections, check:
(a) EARTH CONTINUITY
(b) SHORT CIRCUIT CHECK
(c) POLARITY
(d) RESISTANCE TO EARTH
An optional text display is available which gives a text description of the
service functions of the boiler.
A more detailed fault finding procedure is described in the Service
Engineer's booklet..
This fault finding information is for guidance only. The
Worcester, Bosch Group cannot be held responsible for
costs incurred by persons not deemed to be competent.
Display
code
Description
Remedy
A7
Hot water NTC sensor defective.
Check hot water NTC sensor and connecting lead for circuit breaks/short circuits.
A8
Break in communication to FX controls.
Check electrical connections.
b1
Code plug not detected.
Insert code plug correctly, test and replace if necessary.
C6
Fan speed too low.
Check fan lead and connector, and fan; replace as necessary.
E2
CH flow NTC sensor defective.
Check CH flow NTC sensor and connecting lead.
E9
Safety temp. limiter in CH flow has tripped.
Check system pressure, check safety temp. limiters, check pump operation,
check fuse on pcb, bleed appliance.
EA
Flame not detected/Ignition lockout.
Is gas cock turned on?
Check gas supply pressure, power supply, igniter electrode and lead, ionisation
sensing electrode and lead and CO2 level.
Check the condition of the flue, is it blocked?
Check the condensate pipe, is it blocked or frozen?
F0
Internal error.
Check electrical connector contacts, programmer inter-face module ignition leads
are not loose; replace pcb if necessary.
F7
Flame detected even though appliance switched off. Check electrode assembly, dry pcb. Flue clear?
FA
Flame detected after gas shut off.
Check gas valve and wiring to gas valve. Clean condensation trap and check
electrode assembly. Flue clear?
Fd
Reset button pressed by mistake
Press reset button again
Table 34