background image

STARTING AND STOPPING THE HYBRID SYSTEM

6 720 803 688 (2012/11)

7

4

STARTING AND STOPPING THE HYBRID 
SYSTEM

The specified sequences and delays must always be observed when 
starting and stopping the hybrid system. Otherwise the hybrid system 
components could suffer severe damage.

4.1

STOPPING THE HYBRID SYSTEM

Switching off the hybrid system:

▶ Reset any current heat demands using the programming unit. 
▶ After stopping the operation, wait at least 5 minutes. Only then isolate 

the power supply to the hybrid manager and the external unit. 
Otherwise, water leakage or breakdown may result.

4.2

 ENSURING FROST PROTECTION

4.3

RESTARTING THE HYBRID SYSTEM AFTER AN 
INTERRUPTION IN OPERATION

4.4

SETTING UP HEATING MODE

Make the following adjustments on the condensing boiler or on the 
FW200 programming unit: 

• Maximum flow temperature

With underfloor heating systems observe the maximum permissible flow 
temperature. Older underfloor heating systems generally require higher 
flow temperatures than more modern systems. 

• Maximum DHW temperature
• Setback mode
• Summer  mode
• Frost protection

4.5

SETTING HYBRID SYSTEMS

4.5.1

OVERVIEW OF THE CONTROL MODES

Symbols

Current room temperature

Flashing segment:
Current time (

09:30

 to 

09:45

)

Solid segments: 
Time set for operating mode 

 = Comfort today (1 

segment = 15 min)

Empty segments: 
Time set for operating mode 

 = Economy today (1 

segment = 15 min)

No segments: 
Time set for operating mode 

 = Frost today (1 segment = 

15 min)

Operating mode Comfort for heating circuit

Operating mode Economy for heating circuit

Operating mode Frost for heating circuit

Automatic mode for heating circuit

Holiday mode

Burner operation on display for heating circuit

+

Scroll menu/info text up 
or increase value

– 

Scroll menu/info text down 
or decrease value

OK

Open menu, confirm setting/value or switch heating circuit

Return to next menu up

Delete/reset value

Bring forwards the next switching time and the associated 
operating mode 

 = Comfort

 = Economy
 = Frost

for the heating circuit to now.

Activate DHW heating immediately. The DHW cylinder is 
heated to the required temperature for 60 minutes or, with 
combi boilers, comfort mode is activated for 30 minutes. If 
the ECO button is active for combi boilers, the 

 

button has no function.

The hybrid control module regulates the times the air to 
water heat pump and the condensing boiler are in use, 
subject to the parameters entered into the FW200 
programming unit.
▶ Never isolate the power supply to the hybrid manager 

and the external unit during standard operation.

9

21

15

3

advance

advance

advance

NOTICE: 

Frost damage

When the heating system is switched off, it can freeze up 
if there is a frost. 

▶ In the case of a risk of frost, have the DHW circuit 

drained by an a competent person or mix antifreeze 
that is approved for use with the respective 
condensing boiler into the heating water.

Whether antifreeze may be used and which type is 
permissible depends on the installed condensing boiler.
▶ Observe the details in the condensing boiler 

installation instructions.

NOTICE: 

Damage to the external unit from low operating 

temperature.
When restoring the power supply following an 
interruption of operation.
The Power supply to the external unit must be ‘live’ for at 
least 12 hours before starting operation. This is to 
ensure that the compressor is warmed up sufficiently to 
avoid any liquid refrigerant from entering the 
compressor. This is particularly important during colder 
periods.

The 12 hour period also compensates for any unsettling 
of the lubricating oil within the compressor which may 
have occurred during transportation.
If this 12 hour time period cannot be met damage to the 
outdoor unit may result.

▶ If the appliances fail to start contact your installer.

The separate operating instructions of the condensing 
boiler or the FW200 programming unit include 
information on the steps required. 

These parameters can be set either via the FW 200 
weather-compensated controller or via the hybrid 
control module. These values are transferred and 
overwritten respectively. The following section will 
describe how to make the settings using the FW 200 
weather-compensated controller.

Summary of Contents for GREENSTAR PLUS

Page 1: ...NSTRUCTIONS FOR THE USER HYBRID SYSTEM WITH AIR TO WATER HEAT PUMP GREENSTAR PLUS HYBRID 6720803687 00 1Wo FOR COMBINATION WITH WORCESTER APPLIANCES THAT HAVE A CENTRAL HEATING OUTPUT UP TO 28kW 6 720...

Page 2: ...liance 3 2 1 Designated use 3 2 2 EU Declaration of Conformity 3 2 3 Data plate 4 2 4 General information on heat production 4 2 5 Overview of components 5 2 5 1 Greenstar plus hybrid manager internal...

Page 3: ...nstalled by a competent person Modification for any other use is forbidden Never close the outlets of any safety valves COMMISSIONING Thehybridsystemandthecomponentsmayonlybecommissionedby a competent...

Page 4: ...echnologies in one system and thereby offersthe opportunity to use either heat source optimally at any time Users can decide for themselves whether the emphasis should be on primary energy consumption...

Page 5: ...nager 1 Refrigerant lines for the refrigerant R410A 2 Casing 3 Water pipe connections 2 5 2 GREENSTAR PLUS EXTERNAL UNIT Fig 3 Main components and casing of external unit 4 Top casing panel 5 Service...

Page 6: ...regulated by means of the weather compensated FW200 programming unit 9 12h 15 18 21 24h 3 6 6 720 613 572 01 1O 3 3 4 1 menu info 1 2 3 5 6 7 8 4 Keyboards 1 Turning the selector in direction Selects...

Page 7: ...e heating circuit to now Activate DHW heating immediately The DHW cylinder is heatedto the requiredtemperature for 60minutes or with combi boilers comfort mode is activated for 30 minutes If the ECO b...

Page 8: ...erature CO2 cost mix 4 5 3 MAIN MENU ENERGY PRICE RATIO Thismenuoptionisonlyavailableifthecontrolstrategyhasbeensetto cost optimised or CO2 cost Mix at contractor level Operation Display Open flap The...

Page 9: ...NTENANCE So that gas consumption and environmental impact can be kept as low as possible for as long as possible we recommend that you take out an inspection and maintenance contract with an authorise...

Page 10: ...nst faulty materials or workmanship for a period of two years from the date of installation subject to the following terms and conditions During the period of this guarantee any components of the appl...

Page 11: ...a large proportion of the energy they deliver fromtheenvironment Thisportionofenergyisnotdescribedas supplied energy as it is free of charge Were the efficiency under these conditionstobecalculated i...

Page 12: ...Worcester Bosch Group is a brand name of Bosch Thermotechnology Ltd worcester bosch co uk 6 720 803 688 2012 11 WORCESTER BOSCH GROUP TECHNICAL SUPPORT 0844 892 3366 APPOINTMENTS 0844 892 3000 SPARES...

Reviews: