9. ADMINISTRATOR MODE
9.6.6 Digital
Each ROI has its own measurement result, either positive (pass, OK, condition were met) or negative (fail, NOK
condition were not met). This depends on the critical value compared to measurement value.
Here administrator can select the digital output logic. There are seven digital outputs, each with either low or
high signal. This signal is deduced out of the individual ROI measurement results.
The boolean logic is used to calculate the digital output among selected ROIs. If there is just one ROI checked
for the digital output, the measurement result will apply directly to the digital output. If there are more ROIs
checked for one digital output, the final result (positive or negative) is calculated with the boolean operations
AND, NAND, OR, NOR.
ROI 0
ROI 1
AND
NAND
OR
NOR
0
0
0
1
0
1
0
1
0
1
1
0
1
0
0
1
1
0
1
1
1
0
1
0
Table 9.1: Summarizing table for boolean logic, 1 is positive result and 0 is negative.
This is the short summary of boolean operators:
AND
‐ Positive only if all measurement results of checked ROIs positive
NAND
‐ Opposite of AND, negative only if all measurement results of checked ROIs positive
OR
‐ Positive if at least one measurement results of checked ROIs positive
NOR
‐ Opposite of NOR, positive only if all measurement results of checked ROIs negative
9.6.7 Analog
Select which ROI should display it’s current frame statistic value to which analog output.
9.6.8 Copying ROI settings
Administrator can copy the ROI settings to different ROI with the bottom table selection and ”Copy settings”
button.