WDFC Quick Start Guide

Common Parameters

Group 

Name

Description

See drive manual for complete configuration capabilities

NOTE: Press [ESC] key to escape from a Group

Default 

Value

Value  

Range

New  

Value

CNF-61

Easy Start Settings: 0 = Disabled; 1 = Enabled

1

0-1

CNF-40

CNF-40 = 1 Defaults ALL Groups in VFD: 0 = No; see manual for full selection chart

0

0-15

Restarting the VFD will activate Easy Start on. Set KEYPAD values as follows:

DRV-01

Cmd Frequency: set by the keypad

HZ

Low/High Freq

DRV-06

Command Source: 0 = Keypad; 1 = FX/RX1; 2 = FX/RX2; 3 = Int 485; 4 = Field Bus

3

0-5

DRV-07

Frequency Setting Method: 0 = Keypad1; 2 = V1; 4 = V2; 5 = I2; 6 = Int485; 8 = FldBus

0

0-11

BAS-10

60/50Hz Sel = Set to motor rated frequency

DRV-14

Motor Capacity = Set to motor HP

BAS-11

Pole Number = Set to motor pole number (Example 4-pole = 1800rpm)

BAS-13

Rated Curr = Set to motor rated current

BAS-15

Rated Volt = Set to motor rated voltage

BAS-19

AC Input Voltage = Set to AC Line Voltage to VFD

PRT-08

Reset Restart: Set Bit 00 or 11

0

11

PRT-09

Restart number of attempts

0

0-9

Drive Group

DRV01

Cmd Frequency: set by the keypad

Hz

Low/High Freq

DRV02

Keypad - VFD Run Direction: 0= Reverse; 1 = Forward

Fwd

Fwd/Rev

DRV03

Accel time in seconds

20.0

0.0-600.0

DRV04

Decel time in seconds

30.0

0.0-600.0

DRV06

Command Source: 0 = Keypad; 1 = FX/RX2; 3 = Int 484; 4 = Field Bus

3

0-5

DRV07

Frequency Setting Method: 0 = Keypad1; 2 = V1; 4 = V2; 5 = I2; 6 = Int485; 8 = Fld Bus

0

0-11

DRV09

Control Mode: 0 = V/F; 1 = Slip Comp; 2 = Resv; 3 = IM Sensorless; 4 = PM Sensorless

V/F

0-4

DRV14

Motor HP size / capacity

.5-800

DRV15

Torque Boost: 0 = Manual; 1 = Auto; 2 = Auto 2

Manual

0-2

DRV18

Base Frequency: VFD output frequency when running at rated voltage

60.00

30-400hz

DRV19

Start Frequency: frequency VFD starts voltage output

0.50

0.01-10.00hz

DRV20

Maximum Frequency in Hz: set upper & lower frequency limits

60.00

4.00-500.00Hz

DRV21

Displayed units: Hz/RPM Select: 0=Hz Display and 1 = RPM Display

0

0-1

DRV30

kW/HP Unit Selection: 0 = kW; 1 = HP

kW

0-1

BAS

Basic Group

0

BAS07

V/F Pattern: 0 = Linear; 1 = Square; 2 = User V/F; 3 = Square 2

0

0-3

BAS09

Time scale for Acc/Dec Ramps: 0 = 0.01 sec; 1 = 0.1 sec; 2 = 1 sec

0

0-2

BAS10

Base frequency: 0 = 60Hz; 1 = 50 Hz (input power freq)

60.00

60/50Hz

BAS11

Motor pole number (total poles - NOT pole pairs): Ex: 4-pole = 1800rpm motor

4

2~48

BAS13

Rated Current: Motor nameplate Full Load Amps

BAS14

Motor No Load Current in Amps (typical value of 20-40% of FLA)

BAS15

Motor rated voltage: VFD model specific

230/460v

BAS19

VFD AC input power voltage

230/460v

BAS20

Auto tuning: 0=None; 1=All Rotation; 2=All Static; 3=Rotate Lsigma; 6=Static

0

0~6

ADV

Advanced Group

ADV01

Acc Pattern: 0=Linear and 1 = S-Curve

ADV02

Decel Pattern: 0=Linear and 1 = S-Curve

ADV08

Stop mode: 0 = Decel; 1 = DC Brake; 2 = Free Run; 3 = Resv; 4 = Power braking

0

0-4

ADV09

Run Prevent: 0 = None; 1 = FWD Prevent; 2 = REV Prevent

0

0-2

ADV24

Frequency limit: 0= No; 1 = Yes: must enable to set ADV25 & ADV26

0

0-1

ADV25

Frequency low limit: 0.0 to high limit

0.50

0-400 hz

ADV26

Frequency high limit: minimum frequency to maximum frequency

60.00

0.1-400 hz

ADV64

Cooling fan control: 0 = During Run; 1 = Always On; 2 = Temp Control

0

0-2

Note: Shaded areas above denote most frequently used parameters

Summary of Contents for WorldDrive WDFC Series

Page 1: ...pyright 2019 WorldWide Electric Corporation The Globe icon is a registered trademark of WorldWide Electric Corporation WORLDWIDEELECTRIC NET Quick Start Guide WORLDDRIVE WDFC This Quick Start Guide is...

Page 2: ...or during operation Doing so may result in serious injury death or serious property damage Do not open the cover of the VFD even when the power supply to the VFD has been turned off unless it is nece...

Page 3: ...emove screw and wiring cover 2 Wire the incoming power to terminals R L1 S L2 T L3 3 For single phase input applications use R L1 and T L3 4 Wire the motor to terminals U V W 5 Be sure to connect the...

Page 4: ...Pump 6 Vacuum Pump 7 Constant Torq Sample Motor Nameplate EzStart N STP 0 0Hz 99 Start Easy Set 0 1 No Yes D C BAS10 60 50 Hz Sel 1 0 50 Hz 60 Hz DC EzStart N STP 0 0Hz DRV14 Motor Capacity 7 5 0 HP D...

Page 5: ...e voltage Sample Motor Nameplate EzStart N STP 0 0Hz BAS13 Rated Curr 0 0 1000 0 A D 3 6 C 8 0 8 0 A EzStart N STP 0 0Hz BAS15 Rated Volt 170 480 V D 0 C 0 460V EzStart N STP 0 0Hz BAS11 Pole Number 2...

Page 6: ...On the Keypad and monitor your Speed Hz 3 Select the Off Button to stop operation VERIFY MOTOR ROTATION DRV06 Cmd Source 1 Fx Rx 1 DC 2 Fx Rx 2 0 Keypad EzStart N STP 0 0Hz DRV07 Freq Ref Src EzStart...

Page 7: ...A01 Bias 0 0 4 A01 Filter 5ms 6 A01 Monitor 0 0 7 AO2 Mode Frequency 8 A02 Gain 100 0 9 A02 Bias 0 0 10 A02 Filter 5ms 12 A02 Monitor 0 0 31 Relay 1 Trip 32 Relay 2 Run 33 Relay 3 None 34 Relay 4 None...

Page 8: ...4 V2 5 I2 6 Int485 8 Fld Bus 0 0 11 DRV09 Control Mode 0 V F 1 Slip Comp 2 Resv 3 IM Sensorless 4 PM Sensorless V F 0 4 DRV14 Motor HP size capacity 5 800 DRV15 Torque Boost 0 Manual 1 Auto 2 Auto 2...

Page 9: ...lean Mode 1 0 None 1 DI Dependent 2 Output Power 3 Output Current 0 AP2 16 Pump Clean Mode 2 0 None 1 Start 2 Stop 3 Start Stop 0 AP2 38 Decel Valve Freq in Hertz 40 00 AP2 39 Decel Valve Freq in seco...