WorldWide Electric Motor WDFC Quick Start Guide
This guide and all referenced information is intended for qualified personnel only.
For additional information, please consult the WDFC User Manual
1-800-808-2131
8
WDFC Quick Start Guide
Common Parameters
Group
Name
Description
See drive manual for complete configuration capabilities
NOTE: Press [ESC] key to escape from a Group
Default
Value
Value
Range
New
Value
CNF-61
Easy Start Settings: 0 = Disabled; 1 = Enabled
1
0-1
CNF-40
CNF-40 = 1 Defaults ALL Groups in VFD: 0 = No; see manual for full selection chart
0
0-15
Restarting the VFD will activate Easy Start on. Set KEYPAD values as follows:
DRV-01
Cmd Frequency: set by the keypad
HZ
Low/High Freq
DRV-06
Command Source: 0 = Keypad; 1 = FX/RX1; 2 = FX/RX2; 3 = Int 485; 4 = Field Bus
3
0-5
DRV-07
Frequency Setting Method: 0 = Keypad1; 2 = V1; 4 = V2; 5 = I2; 6 = Int485; 8 = FldBus
0
0-11
BAS-10
60/50Hz Sel = Set to motor rated frequency
DRV-14
Motor Capacity = Set to motor HP
BAS-11
Pole Number = Set to motor pole number (Example 4-pole = 1800rpm)
BAS-13
Rated Curr = Set to motor rated current
BAS-15
Rated Volt = Set to motor rated voltage
BAS-19
AC Input Voltage = Set to AC Line Voltage to VFD
PRT-08
Reset Restart: Set Bit 00 or 11
0
11
PRT-09
Restart number of attempts
0
0-9
Drive Group
DRV01
Cmd Frequency: set by the keypad
Hz
Low/High Freq
DRV02
Keypad - VFD Run Direction: 0= Reverse; 1 = Forward
Fwd
Fwd/Rev
DRV03
Accel time in seconds
20.0
0.0-600.0
DRV04
Decel time in seconds
30.0
0.0-600.0
DRV06
Command Source: 0 = Keypad; 1 = FX/RX2; 3 = Int 484; 4 = Field Bus
3
0-5
DRV07
Frequency Setting Method: 0 = Keypad1; 2 = V1; 4 = V2; 5 = I2; 6 = Int485; 8 = Fld Bus
0
0-11
DRV09
Control Mode: 0 = V/F; 1 = Slip Comp; 2 = Resv; 3 = IM Sensorless; 4 = PM Sensorless
V/F
0-4
DRV14
Motor HP size / capacity
.5-800
DRV15
Torque Boost: 0 = Manual; 1 = Auto; 2 = Auto 2
Manual
0-2
DRV18
Base Frequency: VFD output frequency when running at rated voltage
60.00
30-400hz
DRV19
Start Frequency: frequency VFD starts voltage output
0.50
0.01-10.00hz
DRV20
Maximum Frequency in Hz: set upper & lower frequency limits
60.00
4.00-500.00Hz
DRV21
Displayed units: Hz/RPM Select: 0=Hz Display and 1 = RPM Display
0
0-1
DRV30
kW/HP Unit Selection: 0 = kW; 1 = HP
kW
0-1
BAS
Basic Group
0
BAS07
V/F Pattern: 0 = Linear; 1 = Square; 2 = User V/F; 3 = Square 2
0
0-3
BAS09
Time scale for Acc/Dec Ramps: 0 = 0.01 sec; 1 = 0.1 sec; 2 = 1 sec
0
0-2
BAS10
Base frequency: 0 = 60Hz; 1 = 50 Hz (input power freq)
60.00
60/50Hz
BAS11
Motor pole number (total poles - NOT pole pairs): Ex: 4-pole = 1800rpm motor
4
2~48
BAS13
Rated Current: Motor nameplate Full Load Amps
BAS14
Motor No Load Current in Amps (typical value of 20-40% of FLA)
BAS15
Motor rated voltage: VFD model specific
230/460v
BAS19
VFD AC input power voltage
230/460v
BAS20
Auto tuning: 0=None; 1=All Rotation; 2=All Static; 3=Rotate Lsigma; 6=Static
0
0~6
ADV
Advanced Group
ADV01
Acc Pattern: 0=Linear and 1 = S-Curve
ADV02
Decel Pattern: 0=Linear and 1 = S-Curve
ADV08
Stop mode: 0 = Decel; 1 = DC Brake; 2 = Free Run; 3 = Resv; 4 = Power braking
0
0-4
ADV09
Run Prevent: 0 = None; 1 = FWD Prevent; 2 = REV Prevent
0
0-2
ADV24
Frequency limit: 0= No; 1 = Yes: must enable to set ADV25 & ADV26
0
0-1
ADV25
Frequency low limit: 0.0 to high limit
0.50
0-400 hz
ADV26
Frequency high limit: minimum frequency to maximum frequency
60.00
0.1-400 hz
ADV64
Cooling fan control: 0 = During Run; 1 = Always On; 2 = Temp Control
0
0-2
Note: Shaded areas above denote most frequently used parameters