background image

7

FORLI'    Italy

5.3.1 OIL CHANGE

Use detergent oil for four-stroke engines, class API SG or SF
(indicated on the oil can) with SAE viscosity suitable for the
climate (see table).
To allow the oil to drain out easier, run the engine for about
3÷5 minutes. Then discharge the oil when the engine is still
warm so that the emptying is quicker and more complete via
the drainage hose (pos. 2 fig. 8 and 15) by removing the
drain cap (pos. 8 fig. 8 and 15).
Top up with oil of the recommended type via the filling cap
(pos. 9 fig. 8).
Table 2 shows the amount of oil in the oil pan.

Mod.

Liters

1000

0.45

2500

0.6

3000

0.6

4000

1.1

5500

1.1

TAB. 2

DANGER

Warm oil may burn you.

Running the engine with a poor amount of oil can
seriously damage the engine itself.

Check the oil level when engine is stopped.

IMPORTANT

Used oils must never be poured on the ground. They shall
be collected and consigned to qualified companies for the
disposal in accordance with any local regulations.

5.3.2 AIR FILTER MAINTENANCE

IMPORTANT

A dirty air filter reduces the air flow to the carburettor. To
keep the carburettor working properly, check it often. Check
more frequently if the engine is used in dusty areas.

DANGER

Never use diesel oil or solvents with a low evaporation point
for cleaning the air filter, since this may lead to danger of
flames or explosion.

Never let the engine run without the air filter. It would get
damaged in a short space of time.

1. Carefully check both cartridges. Replace them if there

are holes or tears (mod. 1000 H/HG is fitted with a single
cartridge).

2. Sponge cartridge: wash it with a neutral detergent

solution and rinse carefully. Let the cartridge dry
completely, then soak it in clean engine oil and wring out
the excess.

3. Paper cartridge: smoothly beat it several times on a hard

surface to remove any dirt, or blow compressed air
through the filter from inside to out. Do not brush the dirt:
this operation would just push it into the fibres. If the
paper cartridge is too dirty, replace it.

5.3.3 SPARK PLUG MAINTENANCE

RECOMMENDED SPARK PLUG:
Mod. 1000

BMR-4A (980073-54744)

NGK

BPMR4A-10 (98073-54941) NGK

Mod. 2500/3000/4000/5500

BP6ES, BPR6ES

NGK

W20EP-U, W20EPR-U

ND

Never use a spark plug with a different thermal degree.
1. Remove the spark plug nipple (pos. 1 fig. 8) and use a

suitable wrench to remove the spark plug.

2. Visually check the spark plug. If it is worn or if the

insulator is broken or chipped, replace it. Clean the
spark plug with an iron brush if it is to be used again.

3. Measure the electrode distance by means of a thickness

gauge.
The distance should be 0.7-0.8 mm.
Adjust, if necessary, by bending the side electrode.

4. Check that the spark plug washer is in good condition

and screw it manually to prevent it being set at an angle.

5. Once mounted, tighten the spark plug using a  wrench

with the right driving torque.

-30

°

-20

°

-10

°

0

10

°

20

°

30

°

40

°

Room Temperature

MULTIGRADE

SG / SF

Hot climates

Cold climates

10W 30

15W 50

Summary of Contents for AIRCO BLIZZARD 1000

Page 1: ...unting the generator 3 2 3 Electrical connections 3 2 3 1 Connection of the battery recharger 3 2 3 2 Connection of the starter battery 3 2 3 3 Connection of the remote control panel 3 2 4 Installing the fuel tank 3 Connection to gas canister 3 3 0 General operation 4 3 1 Description of generator and functioning 4 3 2 Safety advice 4 3 3 Noise levels 4 4 0 Instructions for use 5 4 1 Starting the g...

Page 2: ...00 Kg 114 Mod 5500 Kg 140 1 3 3 OVERALL DIMENSIONS See figg 2 3 4 Model 1000 2500 3000 4000 5500 A mm 470 530 570 660 700 B mm 535 605 650 740 C mm 565 640 680 770 D mm 320 385 385 475 515 E mm 315 290 290 355 510 F mm 260 295 295 310 G mm 27 30 30 62 H mm 360 360 I mm 65 87 113 78 L mm 65 96 97 265 M mm 225 222 230 130 N mm 36 28 25 17 O mm 535 605 650 740 735 P mm 27 30 30 62 55 Q mm 260 295 295...

Page 3: ...set towards the vehicle interior and having the dimensions given in section 1 3 3 needs to be prearranged with exhaust holes and air inlets drilled into the floor and door In addition use an exhaust union fig 4 suppliedasaccessory tobefixeddirectlyontothegenerator casing with screws or rivets In order to prevent the exhaust gas recycling within the compartment place flameproof sealing around the e...

Page 4: ...s Fuel comes to the combustion engine through a pump which is standard fitted on the unit itself 3 2 SAFETY ADVICE Theunitishousedwithinaperfectlyclosedcasing Therefore there is no danger of accidental contacts with hot or moving parts or wires under voltage The door of the unit is fitted with lock and key and should not be left within the reach of children or non authorised persons DANGER The uni...

Page 5: ...do not place your hands or other objects within the duct 4 4 IMPROPER USE DANGER The generator is to be installed by qualified technicians only according to the manufacturer s instructions Thegeneratoristobeusedonlyandexclusivelyforproducing current for mobile vehicles fitted with a standard electrical circuit in keeping with the power supplied by the generator 4 5 USEFUL ADVICES To use the genset...

Page 6: ...it For mod 1000 it is necessary to disconnect the spark plug nipple pos 1 fig 8 since no safety switch is fitted 5 1 NATURE AND FREQUENCY OF CHECKS 5 2 MAINTENANCE OPERATIONS WHICH DO NOT REQUIRE QUALIFIED TECHNICIANS To carry out these operations the generator door first needs to be opened Therefore the following measures should be taken 1 The generator must be stopped with all parts cold 2 Let t...

Page 7: ...It would get damaged in a short space of time 1 Carefully check both cartridges Replace them if there are holes or tears mod 1000 H HG is fitted with a single cartridge 2 Sponge cartridge wash it with a neutral detergent solution and rinse carefully Let the cartridge dry completely then soak it in clean engine oil and wring out the excess 3 Paper cartridge smoothly beat it several times on a hard ...

Page 8: ...the generator voltage using a tester or voltmeter connected to the vehicle s 230V socket or to the terminals pos 17 18 fig 6 and 14 of the generator terminal board The voltage should be between 230 and 240 Volts Ifthesevaluesarenotobtained adjustthecurrentregulation screw pos 32 fig 10 and 15 until they are Rotate clockwise to increase the voltage Rotate anticlockwise to decrease both r p m und vo...

Page 9: ...s ALTERNATOR 1000H 2500H 3000H 4000H 5500H Type Synchronous single phase self regulated self energized two pole brushless Peak max power W 900 2200 2700 3800 5300 For continuous utilization W 800 2000 2400 3500 4500 Voltage frequence 230V 50Hz D C power 12V 25A 12V 10A 12V 10A 12V 10A 12V 10A Rotor insulation class H H H H H H Stator insulation class F F F F F F Cooling Centrifugal fan GENERATOR 1...

Page 10: ...55 FORLI Italy WIRING DIAGRAMS SCHEMI ELETTRICI ELEKTROPLÄNE STROOMSCHEMA S SCHEMAS ELECTRIQUES ESQUEMAS ELÉCTRICOS ...

Page 11: ...s r l Via Virgilio 3 47100 Villanova Forlì Italy Tel 0543 754213 Telefax 0543 756631 AN ELECTROLUX COMPANY ...

Page 12: ...tore leggere attentamente le istruzioni e le indicazioni riportate nel seguente manuale Vor dem Gebrauch des Generators diese Bedienungs und Wartungsanleitung aufmerksam lesen Lees alle aanwijzingen en adviezen in deze handleiding nauwkeurig door voordat u de generator in gebruik neemt Avant d utiliser le générateur lire attentivement les instructions et les renseignements du présent livret Antes ...

Page 13: ...FIG 1 FIG 2 FIG 3 FIG 4 FIG 5 FIG 6 FIG 7 FIG 8 30 28 17 18 16 15 230 V 230 V 12 V 16 17 18 14 13 11 7 10 12 15 1 h 0 0 0 0 0 START I 0 22 6 24 27 26 25 23 E D G F H C A B 2 3 9 8 4 5 21 19 20 1 36 Z Y X FORLI Italy ...

Page 14: ... h 0 0 0 0 0 START I 230 230 12 32 30 32 O 1 C IR CUIT BREA K E R P R E S S T O RE S E T C IR CUIT BREA K E R P R E S S T O RE S E T C IR CUIT BREA K E R P R E S S T O RE S E T 220 220 12 33 32 17 16 15 18 14 7 12 13 11 10 34 35 31 29 FORLI Italy 28 2 8 3 4 36 ...

Reviews: