Hardware Troubleshooting
MedWeld 5000 Technical Reference Manual
9 - 7
M-032170
Control not
responding to
DEP-100S.
Bad connection between timer unit
and DEP-100S.
Check the connection between the timer
unit and DEP-100S.
Check for faulty connector or cable.
If networking, there is no network
supply or external 120 VAC
connected to the power supply (as
required to power the DEP-100S).
Verify that the network power supply is
connected and external 120 VAC is
supplied.
If networking, check for improper or
loose wiring at MedLAN connection.
Check for secure and proper wiring. Refer
to MedLAN wire designations described in
“Providing MedLAN Connections” on
page 2-5.
Two controls share the same
MedLAN address.
Check each control’s address. Verify that
each has a UNIQUE address.
Verify that the DEP-100S software is
compatible with the timer unit. (Con-
sult your WTC representative for
assistance.)
Update software.
Faulty timer, DEP-100S or faulty Net-
work Power Pack.
Replace as necessary.
Control
sequences
without firing.
The control is in No Weld.
Check the status of the WELD/NO WELD
input. Verify that the control and all data
entry devices are in Weld mode.
A fault occurred, causing the control
to complete the weld schedule in No
Weld.
Check the data entry device to determine
any fault conditions. Clear the fault(s),
correct the problem and re-initiate.
Programming error.
Check the weld schedule being initiated to
verify that the weld schedule contains a
weld function. Also verify that the weld
function has a value greater than zero for
the specified number of cycles.
Timer is not sending firing signals.
Remove power from the chassis and
check for faulty connectors or cables and
cycle power.
Is the inverter receiving firing
signals?
If
YES
, check the timer for loose or dis-
connected wires. Also, check to see if fir-
ing into an open primary or secondary of
the weld transformer.
If
NO
, check the timer unit card. Replace
as necessary.
I/O not respond-
ing as expected.
Problem with the I/O.
Check the device supplying the input or
receiving the output.
Incorrect or loose wiring to the timer unit.
Problem
Possible Cause
Possible Solution
Summary of Contents for MedWeld 5000
Page 2: ...MedWeld 5000 Technical Reference Manual Modified 1 31 06 M 032170...
Page 6: ...MedWeld 5000 Technical Reference Manual Modified 1 31 06...
Page 38: ...Installing the MedWeld 5000 2 12 MedWeld 5000 Technical Reference Manual M 032170...
Page 82: ...Advanced Software Features 5 12 MedWeld 5000 Technical Reference Manual M 032170...
Page 120: ...Hardware Troubleshooting 9 10 MedWeld 5000 Technical Reference Manual M 032170...