3.1.1.2.
Broadcast Mode (Sw5)
On (1) forces all ports open. Data from the Control (MODEM)
port is sent to all Input ports. Useful for broadcasting to or
controlling all Input devices. When enabled, concurrent data
sent by Input ports to the Control port will be jumbled together.
Broadcast Mode
Sw5
Disable*
0
Enable
1
* = Factory Setting
3.1.1.3.
Baud Rate Select (Sw6 - Sw8)
Selects the operating baud rate; from 150 to 19.2K baud.
Baud Rate
Switch (Bank 1)
6
7
8
19200
0
0
0
9600*
1
0
0
4800
0
1
0
2400
1
1
0
1200
0
0
1
600
1
0
1
300
0
1
1
150
1
1
1
* = Factory Setting
3.1.2.
SetUp Switch Bank 2
The bank of DIP switches located closest to the front panel are
used to select the Prefix Code character and set the parity.
3.1.2.1.
Prefix Code (Sw1 - Sw7)
As mentioned previously, the Prefix Code informs the unit that
the next character will be a command. The Prefix code can be
any ASCII character. However, since it is passed on to the
connected device, it is recommended to use a non-printable
character. The factory default is ^V (Control V). Please refer to
the following table when selecting a Prefix Code.
3-2
CAS-161A User’s Guide