2-10
Unit Description
2.10. NPS Series - Back Panel
As shown in Figure 2.10, the NPS Series Back Panel includes the following components:
1.
Power Circuit A - Power Inlet:
An IEC320-C20 AC inlet which supplies power to
NPS control functions and the Circuit “A” outlets. Also includes cable keeper
(not shown.)
Notes:
• NPS-8HS series units feature a single Power Inlet.
• NPS-ATS series units feature dual, redundant power inlets.
2.
Power Circuit B - Power Inlet:
An IEC320-C20 AC inlet which supplies power to
NPS control functions and the Circuit “B” outlets. Also includes cable keeper
(not shown.) (Not present on NPS-8HS series units.)
3.
Power Circuit A - Switched Outlets:
AC Outlets that can be switched On, Off,
rebooted or set to default state in response to user commands:
4.
Power Circuit B - Switched Outlets:
Same as Item 3 above. (Not present on
NPS-8HS series units.)
5.
Alarm Indicator Lights:
Two LEDs which light when an alarm condition is
detected at the corresponding power circuit. Note that NPS-8HS series units only
include one power circuit and one Alarm Indicator Light. For information on Alarm
Configuration, please refer to Section 8.
6.
Network Port:
An RJ45 Ethernet port for connection to your 100Base-T, TCP/IP
network. Note that the NPS features a default IP address (192.168.168.168). This
allows you to connect to the unit without first assigning an IP address. Note that the
Network Port also includes two, small LED indicators for Link and Data Activity. For
more information on Network Port configuration, please refer to Section 6.8.