FVB120-PAT 

 

Product information

 

Page 4 of 4 

Subject to technical changes FVB120-PAT_V3.30_PI_2018-01_EN 

Fault inputs that are not used 

In order to obtain correct fault information, fault inputs that are not used must be jumpered with the 
fault signal that is connected upstream within the alarm routing. The input "Operation 1/2" (terminal 
22/26) is used for measuring the operating hours. If no corresponding signal is available from the 
machine protection, then it is advisable to jumper the output relay. 

 

Monitoring function / emergency program

 

In the event of an F-BUS fault, the field module enters an emergency program corresponding to the 
operating mode. 
If a problem with the cover identification arises at the same time, then all of the output relays are 
switched off and the analogue output "A out" is set to 0V. 

 

Module addressing 

Make sure that each of the 8 field modules per master module (HVI-G3/G4: 12) has a different module 
address. Permissible addresses are the values 0-7 (HVI-G3/G4: 0-B). No other settings are permitted. 
The address of the module FIO001B / FIO-PAT and the addresses of the field modules FVBxxxB / 
FVBxxx-PAT must not overlap. In the event of an address collision, an entry is made in the fault list of 
the master module and the LED "

" (fault) on the field modules flashes. 

 

Technical data 

Power supply 

230V~, +10% / -15%, approx. 7VA 

Display 

1 x red LED, flashing in case of fault 
1 x green LED, operating voltage 
2 x green LED, CAN bus data traffic (CAN Tx, CAN Rx) 
8 x yellow LED, for signal at the input 
4 x green LED, for controlling the relays 

Communication 

2 x RJ45 sockets for CAN bus connection, 
with integrated power supply, galvanically isolated 

Digital inputs 

8 x 230V~, galvanically isolated by optocoupler 

Temperature sensor 

1 x TRK277, S1 for cold zone temperature 
1 x TRK277, S2 for suction gas temperature 

Analogue input 

4...20mA, output voltage 18V=, max. 22mA, suction pressure 

Output relay 

4 x normally open contact 230V~, 4(2)A 

Analogue output 

1 x 0...10V=, non-isolated, max. load 10mA 

Connection cross-section 

2.5mm² 

Dimensions 

(WxHxD) 106 x 90 x 58mm (DIN 43880) 

Fastening 

Top-hat rail TH 35-15 or TH 35-7.5 (DIN EN 60715) 

Ambient temperature 

Operation: 0...+55°C, storage: -25...+70°C 

Weight 

About 450g 

CE conformity 

  2014/30/EU (EMC Directive) 

  2014/35/EU (Low Voltage Directive)  

 

EAC conformity 

  TR CU 004/2011 

  TR CU 020/2011 

 

 

RoHS II 

Valid from 

Version 3.30 

 

 

Note! 

  Please observe the detailed descriptions in the chapters of the FRIGOLINK system 

manual.

 

 