TX90 6kVA & 10kVA User’s Manual
Page 19
Uninterruptible Power Supply
P
UPS inner temperature
Viewing the UPS Default Settings
• After the UPS completely starts up, press the (function) key to change the LCD display to figure Q1.
Q1
Buzzer “On”. Use the key to toggle the setting and then save.
Q2
Buzzer “Off”
• Press the key to scroll through the UPS settings. The LCD will display in sequence figure Q1 (buzzer) →
figure R (Self-test) → figure S (Bypass Voltage Windows) → figure T (Output Frequency Synchronization
Window) → figure U (Inverter Output Voltage) → figure V (UPS Operation Mode) → figure W (Output Volt
-
age Micro Tune Value) → figure X (UPS Id) → figure Y (Parallel function status).
• Buzzer and Self-test can only be changed in this mode while the UPS is on. All other settings must be
changed while the inverter is off in this mode. See Changing the UPS Default Settings on page 22.
• Default settings shown below.
R
Self-test is not “On”. Use the key to toggle the setting and then save.