Adjusting Settings in Configuration Mode
975-0822-01-01
49
Setting Name
Setting
Number
Default
Value
Range of
Values
Description
Output Frequency
07
50
50
60
After changing the output frequency setting, turn the unit off and
then on again, in order for the change to take effect.
Output Voltage
08
230
220
230
240
In V
V
Inverter Output Power
Limit (Freedom X 2000 -
230V)
09
2
.
0
0
.
1
to
2
.
0
The wattage setting value can be adjusted by 100-W increments.
Use with Inverter Output Power Limit Timer especially when
pairing with a lithium ion battery. 0.1 is equivalent to 100 W.
Inverter Output Power
Limit Timer
10
300
1
to
300
When the range is from 1 to 20, the timer setting value can be
adjusted by 1-s increments. When the range is from 20 to 300, the
timer setting value can be adjusted by 10-s increments.
Use with Inverter Output Power especially when pairing with a
lithium ion battery. The timer is automatically disabled if the
maximum Inverter Output Power limit is selected.
Transfer Mode
11
APL
APL
(appliance)
UPS
(UPS)
Selecting
APL
- appliance sets the transfer time from line to battery
to 20 ms. Selecting
UPS
(uninterruptible power supply) sets the
transfer time from line to battery to 10 ms.
NOTE
: Do not connect
motor loads when in UPS transfer mode. See
Utility AC Under Voltage
Level
12
170
170
to
220
In V
V
Summary of Contents for 817-2000-12
Page 1: ...Freedom X 2000 230V Inverter Owner s Guide Freedom X 2000 230V 817 2000 12 ...
Page 12: ...This page is intentionally left blank 2 ...
Page 24: ...This page is intentionally left blank 2 ...
Page 52: ...This page is intentionally left blank 2 ...
Page 77: ...This page is intentionally left blank 2 ...