Two-Stage Charging
975-1038-01-01
35
Two-Stage Charging
The two-stage charging mode employs the following sequence:
Bulk and Absorption
. It runs similar to the three-stage sequence
except that there is no float stage; after the absorption stage the
charger stops providing current to the battery and the charger
output drops to 9 V
Z
. In this manner, DC loads draw power
supplied by batteries and the charger enters a “rest or standby
stage.”
Like the three-stage sequence, the charger will restart the
charging cycle in the Bulk stage if the lowest battery voltage of the
banks drops below 12.5 V (12 V
Z
chargers) for 15 minutes. After
21 days, the charger will automatically restart charging in order to
refresh the batteries.
Figure 19 Two-Stage Charging Process
Battery Voltage
Time
9V
ABS
CV
REST
(Standby)
ABS CV timeout
max 5 hrs
REST (Standby)
timeout max 7 days
BULK
GO TO BULK when
Vbat < 12.5 V for
15 minutes
Vbat = Vabs
for 1 minute
for 1 minute
lout < 10% lrating
Charge
start
Start of
charging cycle
Float Only Charging
The float-only charging mode maintains a maximum charging
voltage equal to a preset float voltage. A float stage is applied
steadily to the battery.
Summary of Contents for 819-0120-12
Page 1: ...XPLORE 120A 12V Battery Charger Owner s Guide Model XPLORE 120 12 Battery Charger 819 0120 12...
Page 12: ...This page is intentionally left blank 2...
Page 18: ...This page is intentionally left blank 2...
Page 24: ...This page is intentionally left blank 2...
Page 60: ...This page is intentionally left blank 2...
Page 72: ...975 1038 01 01 Rev C 31021 http www xantrex com 1 800 670 0707 1 408 987 6030 Printed in...