Introduction
1–4
973-0031-01-01 Rev A
Specifications
The following table contains the specifications for the ACCB-L, the ACCB-L-L1,
and the ACCB-L-L2. The ACCB-L-L2 is not available pre-built from the factory,
but is created by field-installing an ACCB-L2-PCK into a ACCB-L-L1 model.
Table 1-1
Operational and Environmental Specifications for the ACCB-L, ACCB-L-L1, and ACCB-L-L2
ACCB-L
ACCB-L-L1
ACCB-L-L2
a
Dimensions
33" (H) x 11" (W) x 8 3/4" (D)
(84 cm x 28 cm x 23 cm)
33"
(H)
x 11" (W) x 8 3/4" (D)
(84 cm x 28 cm x 23 cm)
This configuration is created
by field-installing an ACCB-
L2-PCK into an ACCB-L-
L1.
Weight
19 pounds (8.6 kg)
24 pounds (10.9 kg)
~2 pounds
Shipping Weight
23 pounds (10.4 kg)
27 pounds (12.2 kg)
~2 pounds
Operating Voltage
120/240 Vac,
60 Hz split-phase
120/240 Vac,
60 Hz split-phase
120/240 Vac,
60 Hz split-phase
Factory-installed
hardware
• Din Rail
• Ground Bar
• Din Rail
• Ground Bar
• AC Bus Bar (Neutral)
• AC Bus Bar (HOT L1)
• AC Input/Output Terminals
• AC Bypass Breaker
• Din Rail
• Ground Bar
• AC Bus Bar (Neutral)
• AC Bus Bar (HOT L1)
• AC Input/Output
Terminals
• AC Bypass Breaker
Factory-installed
wiring
None
#6 THHN AWG, rated to
105 °C, stranded copper
• One - Ground Wire
• One - Neutral Wire
• One - H
OT
IN
• One - H
OT
OUT
#6 THHN AWG, rated to
105 °C, stranded copper
• One - Ground Wire
• One - Neutral Wire
• One - H
OT
IN
• One - H
OT
OUT
Field-installed
hardware
N/A
ACCB-L2-PCK (needed to
create ACCB-L-L2)
• AC Bypass Breaker (Din
Rail-mountable) (w/H
OT
In
and H
OT
Out wiring)
• AC Bus Bar (H
OT
L2)
AC Bypass Switch
Bypass
None
60 Amp (SPST)
60 Amp (SPST)
Inverter
Input/Output
None
60 Amp (DPST)
60 Amp (DPST)
Rated Temperature 0 to 25 °C
(32 to 77 °F)
0 to 25 °C
(32 to 77 °F)
0 to 25 °C
(32 to 77 °F)
Storage
Temperature
-55 to +100 °C
(-67 to 212 °F)
-55 to +100 °C
(-67 to 212 °F)
-55 to +100 °C
(-67 to 212 °F)
Enclosure
Indoor rated, White,
Powdercoat Finish
Indoor rated, White,
Powdercoat Finish
Indoor rated, White,
Powdercoat Finish
Summary of Contents for ACCB-L
Page 1: ...Sine Wave Plus Long AC Conduit Box Owner s Guide Owner s Guide ACCB L ACCB L L1...
Page 2: ......
Page 3: ...Sine Wave Plus Long AC Conduit Box Owner s Guide...
Page 12: ...x...
Page 14: ...xii...
Page 22: ...1 8...
Page 63: ......