Specifications
A–2
TM-XR9B-01XN
Specifications for XFR 1.2kW with
Ethernet/RS-232
Interface
Installed
Table A-1
XFR 1.2kW 7.5 V to 40 V
Models
7.5-140
12-100
20-60
35-35
40-30
Program Resolution
Voltage
Current
OVP
1.2mV
18.3mA
1.2mV
3.1mV
7.1mA
3.1mV
5.1mV
4.7mA
5.1mV
5.4mV
5.4mA
5.4mV
6.2mV
3.6mA
6.2mV
Program Accuracy
a
Voltage
Current
OVP
a. Apply accuracy specifications according to the following voltage program accuracy example:
Set a model 20-60 power supply to 10 volts.
The expected result will be within the range of 10 volts ± 75mV ± 0.12% of the set voltage of
10 volts.
10mV
±0.12%
500mA
±0.1%
80mV
75mV
±0.12%
250mA
±0.1%
200mV
75mV
±0.12%
165mA
±0.15%
330mV
75mV
±0.3%
200mA
±0.1%
350mV
75mV
±0.3%
140mA
±0.15%
400mV
Readback Resolution
Voltage
Current
1.2mV
18.3mA
3.1mV
7.1mA
5.1mV
4.7mA
5.4mV
5.4mA
6.2mV
3.6mA
Readback Accuracy
a
Voltage
Current
30mV
±0.12%
500mA
±0.1%
75mV
±0.12%
250mA
±0.1%
75mV
±0.2%
165mA
±0.15%
75mV
±0.3%
200mA
±0.1%
75mV
±0.3%
140mA
±0.15%
TM-XR9B-01XN.book Page 2 Monday, April 19, 2004 9:00 AM
Summary of Contents for ENET-XFR
Page 2: ......
Page 3: ...XFR 1 2kW and 2 8kW Ethernet RS 232 Interface Option Operating Manual...
Page 8: ...vi...
Page 10: ...viii...
Page 14: ...xii...
Page 16: ...xiv...
Page 18: ...xvi...
Page 22: ...1 4...
Page 49: ...User Signals TM XR9B 01XN 2 27 Figure 2 6 User Lines Signal Connector Circuit Block Diagram...
Page 74: ...3 24...
Page 82: ...4 8...
Page 88: ...A 6...
Page 94: ...B 6...
Page 99: ......