Freedom SW Owner’s Guide
Freedom Inverter/Charger Operation
loads and increase the output again when the AC load
decreases. The regulatory maximum for continuous AC loads
is 80% of the breaker rating (see “
that the loads are connected to. The Freedom SW senses pass-
through current going to the AC load. The difference between
the pass-through (load) and 80% of the
AC1 Breaker
setting
is the current that is available for charging the batteries.
For example, if the AC input of the Freedom SW is from an
AC panel with a 30-amp breaker, the
AC1 Breaker
setting on
the SCP should be selected as
30
amps. Based on this, the
charger will control the charge current so that the total current
draw is equal to or less than 24 amps in this case. Should the
load current be more than 24 amps, the charger output will
reduce to 0 amp, but the Freedom SW will continue to supply
the loads. The Freedom SW will continue to pass-through
power to the loads, even if the load current exceeds the
AC1
Breaker
setting. In this case, it will be up to the user to
remove/disconnect loads if tripping the AC input breaker
supplying the Freedom SW is to be avoided.
NOTE
: The
AC1 Breaker
setting can also be changed using
the
Shr
soft key in the SCP (see “Soft Key Navigation” on
Shr
stands for shore power which refers to
incoming AC power in the mobile industry.
FSW Owners Guide.book Page 22 Tuesday, August 7, 2018 9:03 AM
Summary of Contents for Freedom SW 815-2012
Page 2: ...FSW Owners Guide book Page ii Tuesday August 7 2018 9 03 AM ...
Page 14: ...FSW Owners Guide book Page iv Tuesday August 7 2018 9 03 AM ...
Page 30: ...FSW Owners Guide book Page 16 Tuesday August 7 2018 9 03 AM ...
Page 116: ...FSW Owners Guide book Page 102 Tuesday August 7 2018 9 03 AM ...
Page 121: ...FSW Owners Guide book Page i Tuesday August 7 2018 9 03 AM ...