Basic Installation Procedures
975-0787-01-01
25
Connecting the Equipment Ground
WARNING
ELECTRIC SHOCK HAZARD
Never operate the Freedom X without properly connecting the
equipment ground. A shock and energy hazard could result from
improper grounding.
Failure to follow these instructions can result in death, serious
injury, or equipment damage
.
The Freedom X has a ground lug on the side of the unit as shown
in
Connecting the Equipment Ground
. Follow the guidelines in
Connecting the Equipment Ground
to connect the inverter’s
chassis to the ground.
Figure 7 DC Panel Connections
1
1
DC grounding lug
Grounding Locations
You must connect the equipment ground lug to a grounding
point—usually the vehicle’s chassis or DC negative bus ground—
using recommended copper wire (if insulated then green insulation
with or without one or more yellow stripes) or larger.
Make sure to tighten the bolt on the DC ground lug to a torque of
23 in-lb (2.6 N-m) of force. Apply an anti-corrosion compound to
the copper wire prior to connecting to the DC ground lug.