Basic Installation Procedures
26
Freedom X Owner's Guide
For recommended equipment ground cable size, see below.
Application
Minimum equipment ground cable
size (Stranded copper cable is
required)
Recreational
Vehicle
b
No. 8 AWG
Marine
c
No. 3 AWG (Freedom X 1000 120VAC
12VDC)
No. 1/0 AWG (Freedom X 2000 120VAC
12VDC)
No. 2/0 AWG (Freedom X 3000 120VAC
12VDC)
No. 3 AWG (Freedom X 2000 120VAC
24VDC)
NOTE
: There are no restrictions on length for the equipment
ground cable but try to make it as short as practical to a secure
chassis connection. In general, the equipment ground cable size
must not be smaller than one AWG size than the supply cable.
Table 7 Equipment DC ground cable size
b
Based on US National Electrical Code NFPA70, Article 551, par. 551-20c and ANSI/RVIA LV, § 2-5.1.
c
Based on ABYC E-11 § 11.16 and A-31 § 31.6.5.
Step 4: Connecting the AC Input Wires
WARNING
ELECTRIC SHOCK AND FIRE HAZARDS
Make sure wiring is disconnected from all electrical sources before
handling. All wiring must be done in accordance with local and
national electrical wiring codes. Do not connect the output
terminals of the Freedom X to any incoming AC source.
Failure to follow these instructions can result in death, serious
injury, or equipment damage
.
General AC Wiring Considerations
AC Wiring Connectors
Where applicable, connect AC wires with crimp-on splice
connectors. The amount of insulation you strip off individual wires
will be specified by the connector manufacturer and is different for
different types of connectors.
AC and DC Wiring Separation
Do not mix AC and DC wiring in the same conduit or panel. Where
DC and AC wires must cross, make sure they do so at 90
°
to one
another. Consult applicable codes for details about DC and AC
wiring in close proximity to each other.