Operating During Transition Between Grid Mode and Battery Mode
975-0787-01-01
59
Operating During Transition
Between Grid Mode and Battery
Mode
The Freedom X’s advanced power management is capable of
transitioning power from an AC source to DC source within a
fraction of a second and vice-versa.
The Freedom X automatically detects when shore power is
present and when it becomes unavailable or drops to less than
90 volts AC.
The transfer time can be set to two settings. For details see
Adjusting Feature Settings in Configuration Mode on page 51
.
NOTICE
EQUIPMENT DAMAGE
l
When the transfer mode is set to
UPS
, connect only
sensitive digital equipment that requires fast AC transfer
times.
l
Appliances with motors, compressors, and heating
elements do not require a transfer mode of
UPS
. Set
APL
for
these devices to avoid damaging the transfer relay.
Failure to follow these instructions can result in equipment
damage.
Transitioning from Grid Mode to
Battery Mode
When the unit is operating in grid mode and shore power is lost,
the Freedom X has less than 20 milliseconds (default) to switch to
operating in battery mode (if the Power button is pressed in the On
position) and starts drawing power from the battery.
The operating mode indicator will change to Battery Mode and the
green Status LED for Battery Mode will light up.
However, if the Power button is in Standby mode, this transition
does not happen and the display panel turns off.