Monitoring the Inverter
5–10
975-0466-01-01
Special Screens
Special message screens are displayed in specific situations that are not
considered fault situations. They can appear in any mode of operation. These
screens are described in Table 5-10.
Custom Screens
Two custom screens are available. The inverter does not display them unless they
are configured using GT-View (see page 3–16). If configured, the custom screens
display as the fourth and fifth screens during the startup sequence. They can also
be viewed by tapping the unit during normal operation and fault mode.
The first custom screen is intended for the home owner to display information
such as the name or location of the PV array associated with the inverter.
The second custom screen is intended for installers, who can configure the screen
to display, for example, contact information for service.
Table 5-10
Special Message Screens
Display
Description
Reconnecting in
sss seconds
Time remaining in seconds (sss) before the GT Inverter
reconnects to the Grid. This is a protection timer that runs at
startup and after any Grid fault.
Inverter
Offline
GT Inverter switching (or has switched) from Normal
Operation to Offline mode. This screen may flash alternately
with a Fault message screen.
System *3500W
Today 15.56kWh
The asterisk (
*
) in these two screens (see Table 5-2 and
Table 5-4) indicates that the unit is derating its output power
because the inverter heat sink temperature is above 75 °C or
79 °C depending on model.
The asterisk only appears when the power is actually being
limited by the inverter.
Unit *1800W
Today 7.82kWh
Insufficient
Solar Energy
Indicates the GT Inverter is not producing power due to
insufficient solar energy during low light conditions in early
morning or late afternoon or when the PV array is in shade.
This screen flashes alternately with the Normal Operation
default screen.
Summary of Contents for GT2.8-AU-QC-230
Page 1: ...Xantrex Grid Tie Solar Inverter Owner s Manual GT2 8 AU QC 230 GT5 0 AU QC 230 ...
Page 2: ......
Page 3: ...Xantrex Grid Tie Solar Inverter Owner s Manual ...
Page 8: ...vi ...
Page 14: ...Contents xii 975 0466 01 01 ...
Page 16: ...xiv ...
Page 18: ...xvi ...
Page 58: ...4 4 ...
Page 70: ...Monitoring the Inverter 5 12 975 0466 01 01 ...
Page 76: ...Maintenance and Troubleshooting 6 6 975 0466 01 01 ...
Page 82: ...A 6 ...
Page 89: ......