Operator Interface
152379 Rev C
2–11
Table 2-2
Read Menu Descriptions
Operational Parameter
Description
ID
Units
Current Operating State
Displays as:
System: *
where * can be any one of the states
listed in the description for this
parameter.
Current system states include the following.
Initializing (0)
Key-disabled (1)
Shutdown (2)
Starting (3)
PWR Tracking (4)
Manual Current (5)
Matrix Test (6)
Faulted (7)
1
N/A
System Goal State
Displays as:
Goal: *
where * can be any one of the states
listed in the description for this
parameter.
Goal States include the following.
Shut Down (0)
PWR Tracking (1)
Manual Current (2)
Matrix Test (3)
2
N/A
Fault code
See “Faults and Fault Codes” on page 4–2 for a detailed list
of Fault Codes.
3
N/A
Inverter State
Displays as:
INV: *
where * can be any one of the states
listed in the description for this
parameter.
Inverter States includes the following.
Shut Down (0)
Stand-by (1)
Starting (2)
Main-Setting (3)
On-Line (4)
4
N/A
Line A–B voltage
Displays as:
INV A volts: xxx
Line to line voltage
5
V
rms
Line B–C voltage
Displays as:
INV B volts: xxx
Line to line voltage
6
V
rms
Line C–A voltage
Displays as:
INV C volts: xxx
Line to line voltage
7
V
rms
Phase A current
Displays as:
INV A amps: xxx
Phase A current
8
A
rms
Phase B current
Displays as:
INV B amps: xxx
Phase B current
9
A
rms
Phase C current
Displays as:
INV C amps: xxx
Phase C current
10
A
rms
Summary of Contents for PV100S-208
Page 2: ......
Page 3: ...s PV100S 100 kW Grid Tied Photovoltaic Inverter Operation and Maintenance Manual...
Page 8: ...vi...
Page 14: ...xii...
Page 22: ...xx...
Page 78: ...2 38...
Page 86: ...3 8...
Page 104: ...5 8...
Page 109: ...Appendix A Schematics 152379 Rev C A 5 Figure A 1 Electrical Diagram sample...
Page 116: ...Schematics Appendix A A 12 152379 Rev C This page intentionally left blank...
Page 120: ...Warranty and Return WA 4 152379 Rev C...
Page 123: ......