System Configuration
2–14
976-0043-01-02
and inverter amperage per NEC/CEC guidelines. It is recommended that
the cable has battery acid resistant insulation and is rated for 90 °C
(32 °F) or better.
Be sure to check with any local regulatory agencies for additional
requirements.
Battery cable lugs
Battery cables must have crimped copper compression lugs or crimped
and soldered copper compression lugs. Soldered connections alone are
not acceptable.
High quality battery cables are available from Xantrex in an assortment of
lengths from 1½ to 10 feet in #2/0 AWG and from 1½ to 15 feet in
#4/0 AWG sizes. These cables are color-coded with pressure crimped,
sealed ring terminals.
Overcurrent
protection
For safety and compliance with regulations, battery overcurrent
protection is required. Fuses and disconnects must be sized to protect the
wiring in the system and are required to open before the wire reaches its
maximum current carrying capability.
Xantrex DC175 and
DC250
The NEC/CEC requires both overcurrent protection and a disconnect
switch for residential and commercial electrical systems. These items are
not supplied as part of the inverter. However, Xantrex offers a DC circuit
breaker disconnect module specifically designed for use with Xantrex
Table 2-2
Recommendced Battery Cable Size Versus Length
Inverter
Model
Maximum
Continuous
DC amps
a
a.
“Maximum Continuous DC amps”, as shown in this table, is based on low
battery voltage with an efficiency of 85%.
NEC
amps
b
b.
“NEC amps”, as shown in this table, is based on low battery voltage, and
efficiency of 85%, and a 125% NEC derating.
Up to 5 Feet
One-way
Up to 10 Feet
One-way
Up to 15 Feet
One-way
2524
134
167
#2/0 AWG
(67.4 mm
2
)
#4/0 AWG
(107 mm
2
)
Not
Recommended
2548
67
84
#2/0 AWG
(67.4 mm
2
)
#4/0 AWG
(107 mm
2
)
#4/0 AWG x 2
(107 mm
2
x 2)
4024
214
267
#4/0 AWG
(107 mm
2
)
#4/0 AWG x 2
(107 mm
2
x 2)
Not
Recommended
4048
107
134
#2/0 AWG
(67.4 mm
2
)
#4/0 AWG
(107 mm
2
)
Not
Recommended
5548
147
184
#4/0 AWG
(107 mm
2
)
#4/0 AWG x 2
(107 mm
2
x 2)
Not
Recommended
Summary of Contents for SW Plus 2524
Page 2: ......
Page 3: ...Sine Wave Plus Inverter Charger Owner s Manual...
Page 82: ...2 48...
Page 105: ...DC Wiring 976 0043 01 02 3 23 Figure 3 13 DC Connections to a Single Inverter...
Page 107: ...DC Wiring 976 0043 01 02 3 25 Figure 3 14 DC Connections to Dual Inverters...
Page 126: ...3 44...
Page 132: ...4 6...
Page 141: ...Menu Map 976 0043 01 02 5 9 Figure 5 10 User Menu Map Part 2...
Page 143: ...Menu Map 976 0043 01 02 5 11 Figure 5 12 Basic Setup Menu Map Part 2...
Page 145: ...Menu Map 976 0043 01 02 5 13 Figure 5 14 Advanced Setup Menu Map Part 2...
Page 146: ...Navigation 5 14 976 0043 01 02 Figure 5 15 Complete User Menu Map...
Page 147: ...Menu Map 976 0043 01 02 5 15 Figure 5 16 Complete Basic Setup Menu Map...
Page 148: ...Navigation 5 16 976 0043 01 02 Figure 5 17 Complete Advanced Setup Menu Map...
Page 250: ...8 32...
Page 274: ...A 16...
Page 308: ...C 18...
Page 312: ...D 4...
Page 316: ...E 4...
Page 338: ...I 6...
Page 342: ...Index IX 4 976 0043 01 02...
Page 343: ......