SETUP MENU – 48 VDC (120 VAC/60HZ) MODELS
To access the SETUP MENU, press the RED and GREEN buttons on your CONTROL PANEL (or
SWRC) at the same time. To exit the Setup Menu, press the ON/OFF MENU button or use the down
MENU HEADING button until you reach the USER MENU (menu headings 1 – 8)
.
MENU HEADING
MENU ITEM
SELECTION
RANGE
DEFAULT
SETTINGS
USER
SETTINGS
Inverter Setup
9
Set Grid Usage
FLT SELL SLT LBX
FLT
Set Low Battery cut out VDC
32.0 – 70.0
44.0
Set LBCO delay minutes
00 - 255
15
Set Low battery cut in VDC
20.0 – 71.0
52.0
Set High battery cut out VDC
20.0 – 66.0
64.0
Set search watts
00 - 240
48
Set search spacing
20 – 255
59
Battery Charging
10
Set Bulk volts DC
40.0 – 64.0
57.6
Set Absorption time h:m
00:00 – 23:50
02:00
Set Float volts DC
40.0 – 64.0
53.6
Set Equalize volts DC
40.0 – 64.0
57.6
Set Equalize time h:m
00:00 – 23:50
02:00
Set Max Charge amps AC
01 - 35
30
Set Temp Comp
LeadAcid Nicad
LeadAcid
AC Inputs
11
Set Grid (AC1) amps AC
00 - 63
60
Set Gen (AC2) amps AC
00 - 63
30
Set Input lower limit VAC
80 - 111
108
Set Input upper limit VAC
128 - 149
132
Gen Auto Start Setup
12
Set Load Start amps AC
00 - 63
33
Set Load Start delay min
00.0 – 25.5
05.0
Set Load Stop delay min
00.0 – 25.5
05.0
Set 24 hr start volts DC
20.0 – 71.0
49.2
Set 2 hr start volts DC
20.0 – 71.0
47.2
Set 15 min start volts DC
20.0 – 71.0
45.2
Read LBCO 30 sec start VDC
20.0 – 71.0
44.0
Set Exercise period days
00 - 255
30
Set Maximum run time h:m
00:00 – 23:50
08:00
Gen Starting Details
13
Set RY7 Function
GlowStop Run
Run
Set Gen warmup seconds
16 - 255
60
Set Pre Crank seconds
00 - 255
10
Set Max Cranking seconds
00 - 15
10
Set Post Crank seconds
00 - 255
30
Auxiliary Relays R9 R10
14
Set Relay 9 volts DC
20.0 – 71.0
58.0
R9 Hysteresis volts DC
00.2 – 25.6
04.0
Set Relay 10 volts DC
20.0 – 71.0
59.0
R10 Hysteresis volts DC
00.2 – 25.6
04.0
Set Relay 11 volts DC
20.0 – 71.0
60.0
R1 Hysteresis volts DC
00.2 – 25.6
04.0
Bulk Charge Trigger Timer
15
Start Bulk Time H:M
00:00 – 23:50
00:00
Low Battery Transfer (LBX) 16
Set Low Battery transfer VDC
20.0 – 71.0
45.2
Set Low Battery cut in VDC
20.0 – 71.0
52.0
Battery Selling
17
Set Battery Sell volts DC
40.0 – 64.0
53.6
Set Max Sell amps AC
01 - 35
30
Grid Usage Timer
18
Set Start Charge time h:m
00:00 – 23:50
21:00
End Stop Charge time h:m
00:00 – 23:50
21:00