2.0 Installation
©2002 Xantrex Technology Inc. All Rights Reserved.
P/N 975-0049-01-01 Rev A 10/2002
AC Wiring (continued)
Hardwiring the AC Input and Output (if required)
Input Wiring
1.
Install a conduit or strain relief in the rear panel AC IN
knockout hole.
2.
Feed the AC input cord (from the generator or main
utility panel) through the strain relief.
3.
Strip all wires back approximately 3/8 inch (10 mm).
4.
Connect the green/yellow (ground) wire to the lower
terminal on the main PC board.
5.
Connect the blue or white (neutral) wire to the center
terminal on the main PC board.
6.
Connect the brown or black (hot) wire to the upper
terminal on the main PC board.
7.
Torque all screws to 16 inch-lb (1.8 Nm).
8.
Tighten the screws on the strain relief (leave some slack
in the wire before tightening).
9.
Proceed to output wiring.
CAUTION: TO
REDUCE THE RISK
OF FIRE, USE ONLY
AC INPUT CIRCUITS
PROTECTED BY AN
APPROPRIATELY
SIZED DC BRANCH
CIRCUIT BREAKER.
HOT
NEUTRAL
GROUND
Figure 2-15
Wiring AC Input to Terminal Block