Remote Operation
SCPI Commands for Digital Interfaces
Release 3.0
145
Table 4.9
OPERation Status Register
Bit
Bit Weight Bit Name
Description
0
1
CALibrating
Indicates that the supply is in
CALibration Mode.
1
2
SETTling
Not implemented
2
4
RANGing
Not implemented
3
8
SWEeping
Not implemented
4
16
MEASuring
Not implemented
5
32
Waiting for TRIGger
Summary
Indicates if the supply is waiting
for a TRIGger.
6
64
Waiting for ARM Summary Not implemented
7
128
CORRecting
Not implemented
8
256
REGulating Summary
Reflects the summary of the
REGulating Sub-Register.
9
512
SHUTdown Summary
Reflects the summary of the
SHUTdown Sub-Register.
10
1024
Remote CONtrol
Summary
Reflects the summary of the
Remote CONtrol Sub-Register.
11
2048
Current SHareSummary
Reflects the summary of the
Current Share Sub-Register.
12
4096
Not Used
Not used
13
8192
INSTrument Summary
Not implemented
14
16384
PROGram Running
Indicates that an Automated
Sequence is running.
15
32768
Not Used
Not used
Summary of Contents for XDC
Page 2: ......
Page 3: ...Operating Manual for XDC 6000 Watt and 12000 Watt Series Digital Programmable DC Power Supply ...
Page 22: ...List of Figures xx Operating Manual for XDC Series Power Supply ...
Page 180: ...Current Sharing 6000 Watt only Operation 178 Operating Manual for XDC Series Power Supply ...
Page 216: ...SCPI Command Reference Expressions 214 Operating Manual for XDC Series Power Supply ...
Page 228: ...GPIB Performance Specifications 226 Operating Manual for XDC Series Power Supply ...
Page 253: ......