Local Operation
Standard Operation
Release 3.1
59
Shipped
Configuration
The factory ships units already configured for local control (front panel) operation.
See Table 3.1
for a summary of this configuration.
Table 3.1
Shipped Configuration (Local Control Mode)
Local Control Configuration
Additional References
Use the front panel controls to adjust the output
voltage and current limit settings. (Note: Use
the LOCAL button only when you have a digital
programming interface installed.)
See Section 3
for front panel
operation. See Section 4
for remote
analog programming procedure(s).
The supply’s sense point is at the rear panel
J10 sense connector terminals.
See
“Local and Remote Sensing”
on page 53
for how to change from
local to remote sensing.
The OVP set point is adjusted at the front panel
to approximately 110% of rated output voltage.
See
“Using Over Voltage
Protection (OVP)” on page 61
for
the adjustment procedure.
The over temperature shutdown function
automatically resets when activated as
determined by the position of rear panel switch
SW1-8. A latch off setting is also available.
See
“Over Temperature Protection
(OTP)” on page 70
for more
information about switch SW1-8
settings.